Table of Contents

Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2026.07.17 10:27

Tabular Output Report in Format: HTML

Building: Local comercial - Guía de aplicación DB HE 2019. EJEMPLOS (IV)

Environment: RUNPERIOD 1 ** B3_peninsula - ESP CTE_DB_HE WMO#=

Simulation Timestamp: 2026-07-17 10:27:17


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kWh] Energy Per Total Building Area [kWh/m2] Energy Per Conditioned Building Area [kWh/m2]
Total Site Energy 29881.15 132.13 134.26
Net Site Energy 29881.15 132.13 134.26
Total Source Energy 42314.69 187.11 190.13
Net Source Energy 42314.69 187.11 190.13


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 2.368
Natural Gas 1.195
District Cooling 1.184
District Heating 1.299
Steam 0.250
Gasoline 0.000
Diesel 0.000
Coal 1.084
Fuel Oil No 1 1.182
Fuel Oil No 2 0.000
Propane 1.204
Other Fuel 1 1.037
Other Fuel 2 1.113


Building Area

Area [m2]
Total Building Area 226.15
Net Conditioned Building Area 222.56
Unconditioned Building Area 3.59


End Uses

Electricity [kWh] Natural Gas [kWh] Gasoline [kWh] Diesel [kWh] Coal [kWh] Fuel Oil No 1 [kWh] Fuel Oil No 2 [kWh] Propane [kWh] Other Fuel 1 [kWh] Other Fuel 2 [kWh] District Cooling [kWh] District Heating [kWh] Water [m3]
Heating 173.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 803.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1649.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 580.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 68.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26605.77 505.84
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 3275.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26605.77 505.84
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kWh] Natural Gas [kWh] Gasoline [kWh] Diesel [kWh] Coal [kWh] Fuel Oil No 1 [kWh] Fuel Oil No 2 [kWh] Propane [kWh] Other Fuel 1 [kWh] Other Fuel 2 [kWh] District Cooling [kWh] District Heating [kWh] Water [m3]
Heating General 173.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 803.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1 1649.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 580.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 68.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26605.77 505.84
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [kWh] Natural Gas [kWh] Gasoline [kWh] Diesel [kWh] Coal [kWh] Fuel Oil No 1 [kWh] Fuel Oil No 2 [kWh] Propane [kWh] Other Fuel 1 [kWh] Other Fuel 2 [kWh] District Cooling [kWh] District Heating [kWh] Water [m3]
Heating Unassigned 173.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 803.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 1649.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 580.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 68.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26605.77 505.84
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kWh/m2] Natural Gas Intensity [kWh/m2] Gasoline Intensity [kWh/m2] Diesel Intensity [kWh/m2] Coal Intensity [kWh/m2] Fuel Oil No 1 Intensity [kWh/m2] Fuel Oil No 2 Intensity [kWh/m2] Propane Intensity [kWh/m2] Other Fuel 1 Intensity [kWh/m2] Other Fuel 2 Intensity [kWh/m2] District Cooling Intensity [kWh/m2] District Heating Intensity [kWh/m2] Water Intensity [m3/m2]
Lighting 7.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 4.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 119.55 2.27
Other 2.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 14.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 119.55 2.27


Utility Use Per Total Floor Area

Electricity Intensity [kWh/m2] Natural Gas Intensity [kWh/m2] Gasoline Intensity [kWh/m2] Diesel Intensity [kWh/m2] Coal Intensity [kWh/m2] Fuel Oil No 1 Intensity [kWh/m2] Fuel Oil No 2 Intensity [kWh/m2] Propane Intensity [kWh/m2] Other Fuel 1 Intensity [kWh/m2] Other Fuel 2 Intensity [kWh/m2] District Cooling Intensity [kWh/m2] District Heating Intensity [kWh/m2] Water Intensity [m3/m2]
Lighting 7.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 4.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 117.65 2.24
Other 2.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 14.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 117.65 2.24


Electric Loads Satisfied

Electricity [kWh] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 3275.383 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 3275.383 100.00
     
Total On-Site and Utility Electric Sources 3275.383 100.00
Total Electricity End Uses 3275.383 100.00


On-Site Thermal Sources

Heat [kWh] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 736.16 25.98
Air to Air Heat Recovery for Heating 2097.90 74.02
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 2834.06 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 505.84 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 505.84 100.00
Total Water End Uses 505.84 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 1.00
Tolerance for Zone Cooling Setpoint Not Met Time 1.00


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 4.50
Time Setpoint Not Met During Occupied Cooling 8.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 1850.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Annual Thermal Resilience Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

General

Value
Program Version and Build EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2026.07.17 10:27
RunPeriod RUNPERIOD 1
Weather File B3_peninsula - ESP CTE_DB_HE WMO#=
Latitude [deg] 40.68
Longitude [deg] -4.1
Elevation [m] 667.00
Time Zone 1.00
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 347.82 102.60 49.89 144.89 50.44
Above Ground Wall Area [m2] 303.92 102.60 49.89 100.99 50.44
Window Opening Area [m2] 57.80 9.80 1.86 46.15 0.00
Gross Window-Wall Ratio [%] 16.62 9.55 3.72 31.85 0.00
Above Ground Window-Wall Ratio [%] 19.02 9.55 3.72 45.70 0.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 335.59 96.29 49.89 144.89 44.52
Above Ground Wall Area [m2] 291.69 96.29 49.89 100.99 44.52
Window Opening Area [m2] 57.80 9.80 1.86 46.15 0.00
Gross Window-Wall Ratio [%] 17.22 10.17 3.72 31.85 0.00
Above Ground Window-Wall Ratio [%] 19.82 10.17 3.72 45.70 0.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 12.01
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
Z01_RECEPCION_CAFETERIA 48.00 Yes Yes 164.65 1.00 41.03 0.00 17.95 19.95 3.2498 16.00 3.0000
Z02_OFICINA 5.90 Yes Yes 20.23 1.00 25.83 0.00 7.03 7.81 4.4078 5.90 3.0000
Z03_SALAS_DEPORTIVAS 93.66 Yes Yes 321.26 1.00 124.54 0.00 25.96 29.34 4.1640 4.68 1.0000
Z04_ZONAS_SECAS_P_1 35.26 Yes Yes 106.77 1.00 27.98 16.14 0.00 0.00 2.2123 17.63 0.2424
Z05_VESTUARIOS_P_1 22.97 Yes Yes 69.18 1.00 45.50 14.38 0.00 0.00 0.8490   0.0000
Z06_ASEO_1 3.62 Yes Yes 10.96 1.00 1.27 6.77 0.00 0.00 1.2448   0.0000
Z07_ASEO_2 3.53 Yes Yes 10.71 1.00 1.31 6.62 0.00 0.00 1.2735   0.0000
Z08_ASEO_ACCESIBLE 9.62 Yes Yes 33.00 1.00 24.23 0.00 0.60 0.70 1.2992   0.0000
Z09_ASCENSOR 3.59 No Yes 22.67 1.00 12.23 0.00 0.00 0.00 0.0000   0.0000
Total 226.15     759.41   303.92 43.90 51.53 57.80 3.0555 8.70 1.1670
Conditioned Total 222.56     736.75   291.69 43.90 51.53 57.80 3.1048 8.56 1.1858
Unconditioned Total 3.59     22.67   12.23 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
Z01_RECEPCION_CAFETERIA 48.00 Yes Yes 1.00 Z01_RECEPCION_CAFETERIA GENERAL Z01_RECEPCION_CAFETERIA 3.2498 16.00 3.0000  
Z02_OFICINA 5.90 Yes Yes 1.00 Z02_OFICINA GENERAL Z02_OFICINA 4.4078 5.90 3.0000  
Z03_SALAS_DEPORTIVAS 93.66 Yes Yes 1.00 Z03_SALAS_DEPORTIVAS GENERAL Z03_SALAS_DEPORTIVAS 4.1640 4.68 1.0000  
Z04_ZONAS_SECAS_P_1 35.26 Yes Yes 1.00 Z04_ZONAS_SECAS_P_1 GENERAL Z04_ZONAS_SECAS_P_1 2.2123 17.63 0.2424  
Z05_VESTUARIOS_P_1 22.97 Yes Yes 1.00 Z05_VESTUARIOS_P_1 GENERAL Z05_VESTUARIOS_P_1 0.8490 0.00 0.0000  
Z06_ASEO_1 3.62 Yes Yes 1.00 Z06_ASEO_1 GENERAL Z06_ASEO_1 1.2448 0.00 0.0000  
Z07_ASEO_2 3.53 Yes Yes 1.00 Z07_ASEO_2 GENERAL Z07_ASEO_2 1.2735 0.00 0.0000  
Z08_ASEO_ACCESIBLE 9.62 Yes Yes 1.00 Z08_ASEO_ACCESIBLE GENERAL Z08_ASEO_ACCESIBLE 1.2992 0.00 0.0000  
Z09_ASCENSOR 3.59 No Yes 1.00 Z09_ASCENSOR GENERAL Z09_ASCENSOR 0.0000 0.00 0.0000  
Total 226.15             3.0555 8.70 1.1670  
Conditioned Total 222.56             3.1048 8.56 1.1858  
Unconditioned Total 3.59             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 226.15 222.56 3.59 0.00 3.0555 8.70 1.1670
Total 226.15 222.56 3.59 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] District Heating [W] Water [m3/s]
Time of Peak 20-AUG-16:30 - - - - - - - - - - 01-JAN-00:30 01-JAN-00:30
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1283.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 609.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 96.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 60.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3284.43 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 2050.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3284.43 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] District Heating [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 1283.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1 609.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 96.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 60.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3284.43 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kWh] Source Natural Gas [kWh] Source Gasoline [kWh] Source Diesel [kWh] Source Coal [kWh] Source Fuel Oil No 1 [kWh] Source Fuel Oil No 2 [kWh] Source Propane [kWh] Source Other Fuel 1 [kWh] Source Other Fuel 2 [kWh] Source District Cooling [kWh] Source District Heating [kWh]
Heating 410.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1902.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3905.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1375.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 162.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34558.58
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 7756.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34558.58


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kWh/m2] Source Natural Gas [kWh/m2] Source Gasoline [kWh/m2] Source Diesel [kWh/m2] Source Coal [kWh/m2] Source Fuel Oil No 1 [kWh/m2] Source Fuel Oil No 2 [kWh/m2] Source Propane [kWh/m2] Source Other Fuel 1 [kWh/m2] Source Other Fuel 2 [kWh/m2] Source District Cooling [kWh/m2] Source District Heating [kWh/m2]
Heating 1.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 8.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 17.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 6.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 0.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 155.28
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 34.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 155.28


Source Energy End Use Components Per Total Floor Area

Source Electricity [kWh/m2] Source Natural Gas [kWh/m2] Source Gasoline [kWh/m2] Source Diesel [kWh/m2] Source Coal [kWh/m2] Source Fuel Oil No 1 [kWh/m2] Source Fuel Oil No 2 [kWh/m2] Source Propane [kWh/m2] Source Other Fuel 1 [kWh/m2] Source Other Fuel 2 [kWh/m2] Source District Cooling [kWh/m2] Source District Heating [kWh/m2]
Heating 1.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 8.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 17.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 6.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 0.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 152.81
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 34.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 152.81



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
UT1_ZONE1_RECUPERACION_DE_CALOR 0.024000
UT1_ZONE2_RECUPERACION_DE_CALOR 0.012500
UT1_ZONE3_RECUPERACION_DE_CALOR 0.160000
UT1_ZONE4_RECUPERACION_DE_CALOR 0.030692
UT1_ZONE5_RECUPERACION_DE_CALOR 0.012632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:TerminalUnit:VariableRefrigerantFlow

Design Size Cooling Supply Air Flow Rate [m3/s] Design Size Heating Supply Air Flow Rate [m3/s] Design Size No Cooling Supply Air Flow Rate [m3/s] Design Size No Heating Supply Air Flow Rate [m3/s]
UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS 0.102349 0.102349 0.102349 0.102349
UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS 0.027260 0.027260 0.027260 0.027260
UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS 0.186405 0.186405 0.186405 0.186405
UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS 0.030692 0.030692 0.030692 0.030692
UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS 0.018549 0.018549 0.018549 0.018549
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS SUPPLY FAN 0.102349
UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS SUPPLY FAN 0.027260
UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS SUPPLY FAN 0.186405
UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS SUPPLY FAN 0.030692
UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS SUPPLY FAN 0.018549
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:VariableRefrigerantFlow

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL 0.102349 1694.23 0.800655
UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL 0.027260 451.24 0.800655
UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL 0.186405 3821.05 0.766897
UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL 0.030692 603.27 0.782634
UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS COOLING COIL 0.018549 307.05 0.800655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:VariableRefrigerantFlow

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Heating Capacity [W]
UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL 0.102349 1694.23
UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL 0.027260 451.24
UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL 0.186405 3821.05
UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL 0.030692 603.27
UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS HEATING COIL 0.018549 307.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirConditioner:VariableRefrigerantFlow

Design Size Rated Total Cooling Capacity (gross) [W] Design Size Rated Total Heating Capacity [W] Design Size Resistive Defrost Heater Capacity [W] Design Size Evaporative Condenser Air Flow Rate [m3/s]
LOOP_VRF1_SYSTEM1_UNIDAD_EXTERIOR_DE_BOMBA_DE_CALOR_VRF 6876.84 6876.84 0.000000 0.783960
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:IdealLoadsAirSystem

User-Specified Maximum Heating Air Flow Rate [m3/s] User-Specified Maximum Cooling Air Flow Rate [m3/s]
Z06_ASEO_1-UT1_ZONE6_IDEAL_LOADS_IDEALLOADSAIRSYSTEM 0.000000 0.000000
Z07_ASEO_2-UT1_ZONE7_IDEAL_LOADS_IDEALLOADSAIRSYSTEM 0.000000 0.000000
Z08_ASEO_ACCESIBLE-UT1_ZONE8_IDEAL_LOADS_IDEALLOADSAIRSYSTEM 0.000000 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR 0.024000 0.024000 0.024000 0.024000 0.024000 0.024000 1.00 1.00 0.024000
LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR 0.012500 0.012500 0.012500 0.012500 0.012500 0.012500 1.00 1.00 0.012500
LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR 0.160000 0.160000 0.160000 0.160000 0.160000 0.160000 1.00 1.00 0.160000
LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR 0.030692 0.030692 0.030692 0.030692 0.030692 0.030692 1.00 1.00 0.030692
LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR 0.012632 0.012632 0.012632 0.012632 0.012632 0.012632 1.00 1.00 0.012632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR OA CONTROLLER 0.024000 0.024000
LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR OA CONTROLLER 0.012500 0.012500
LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR OA CONTROLLER 0.160000 0.160000
LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR OA CONTROLLER 0.030692 0.030692
LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR OA CONTROLLER 0.012632 0.012632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR HEAT RECOVERY 0.024000
LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR HEAT RECOVERY 0.012500
LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR HEAT RECOVERY 0.160000
LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR HEAT RECOVERY 0.030692
LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR HEAT RECOVERY 0.012632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR RETURN FAN 0.024000
LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR SUPPLY FAN 0.024000
LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR RETURN FAN 0.012500
LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR SUPPLY FAN 0.012500
LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR RETURN FAN 0.160000
LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR SUPPLY FAN 0.160000
LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR RETURN FAN 0.030692
LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR SUPPLY FAN 0.030692
LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR RETURN FAN 0.012632
LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR SUPPLY FAN 0.012632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
SHDW_B_01 Mir-SHDW_B_02 |
Z01_S01_E09_G1 OH Mir-Z03_S01_E06_G1 OH | Z01_S01_E07 | Z01_S01_E09 | Z02_S01_E06 | Z02_S01_E07 | Z03_S01_E06 |
Mir-Z01_S01_E09_G1 OH Mir-SHDW_B_01 | Mir-SHDW_B_02 | Z01_S01_E09_G2 OH | Z02_S01_E06_G1 OH | Z03_S01_E06_G2 OH | Z01_S01_E07 | Z01_S01_E09 | Z02_S01_E06 | Z02_S01_E07 | Z03_S01_E06 |
Z01_S01_E09_G2 OH Mir-Z01_S01_E09_G1 OH | Mir-Z03_S01_E06_G1 OH | Z01_S01_E07 | Z01_S01_E09 | Z02_S01_E06 | Z02_S01_E07 | Z03_S01_E06 |
Mir-Z01_S01_E09_G2 OH Mir-SHDW_B_01 | Mir-SHDW_B_02 | Z02_S01_E06_G1 OH | Z01_S01_E07 | Z01_S01_E09 | Z02_S01_E06 | Z02_S01_E07 | Z03_S01_E06 |
Z02_S01_E06_G1 OH Mir-Z01_S01_E09_G1 OH | Mir-Z01_S01_E09_G2 OH | Mir-Z03_S01_E06_G1 OH | Mir-Z03_S01_E06_G2 OH | Z01_S01_E07 | Z01_S01_E08 | Z01_S01_E09 | Z02_S01_E06 | Z03_S01_E06 |
Mir-Z02_S01_E06_G1 OH Mir-SHDW_B_01 | Mir-SHDW_B_02 | Z01_S01_E07 | Z01_S01_E08 | Z01_S01_E09 | Z02_S01_E06 | Z03_S01_E06 |
Z03_S01_E06_G1 OH Z01_S01_E07 | Z01_S01_E09 | Z02_S01_E06 | Z02_S01_E07 | Z03_S01_E06 |
Mir-Z03_S01_E06_G1 OH Mir-SHDW_B_01 | Mir-SHDW_B_02 | Z01_S01_E09_G1 OH | Z01_S01_E09_G2 OH | Z02_S01_E06_G1 OH | Z03_S01_E06_G2 OH | Z01_S01_E07 | Z01_S01_E09 | Z02_S01_E06 | Z02_S01_E07 | Z03_S01_E06 |
Z03_S01_E06_G2 OH Mir-Z01_S01_E09_G1 OH | Mir-Z03_S01_E06_G1 OH | Z01_S01_E07 | Z01_S01_E09 | Z02_S01_E06 | Z02_S01_E07 | Z03_S01_E06 |
Mir-Z03_S01_E06_G2 OH Mir-SHDW_B_01 | Mir-SHDW_B_02 | Z02_S01_E06_G1 OH | Z01_S01_E07 | Z01_S01_E09 | Z02_S01_E06 | Z02_S01_E07 | Z03_S01_E06 |
Z01_S01_E07 Mir-SHDW_B_01 | Mir-SHDW_B_02 | Z01_S01_E09_G1 OH | Mir-Z01_S01_E09_G1 OH | Z01_S01_E09_G2 OH | Mir-Z01_S01_E09_G2 OH | Z02_S01_E06_G1 OH | Mir-Z02_S01_E06_G1 OH | Z03_S01_E06_G1 OH | Mir-Z03_S01_E06_G1 OH | Z03_S01_E06_G2 OH | Mir-Z03_S01_E06_G2 OH | Z01_S01_E08 | Z02_S01_E07 |
Z01_S01_E08 Mir-SHDW_B_01 | Mir-SHDW_B_02 | Z02_S01_E06_G1 OH | Mir-Z02_S01_E06_G1 OH | Z01_S01_E07 | Z02_S01_E07 |
Z01_S01_E09 Z01_S01_E09_G1 OH | Mir-Z01_S01_E09_G1 OH | Z01_S01_E09_G2 OH | Mir-Z01_S01_E09_G2 OH | Z02_S01_E06_G1 OH | Mir-Z02_S01_E06_G1 OH | Z03_S01_E06_G1 OH | Mir-Z03_S01_E06_G1 OH | Z03_S01_E06_G2 OH | Mir-Z03_S01_E06_G2 OH |
Z02_S01_E06 Z01_S01_E09_G1 OH | Mir-Z01_S01_E09_G1 OH | Z01_S01_E09_G2 OH | Mir-Z01_S01_E09_G2 OH | Z02_S01_E06_G1 OH | Mir-Z02_S01_E06_G1 OH | Z03_S01_E06_G1 OH | Mir-Z03_S01_E06_G1 OH | Z03_S01_E06_G2 OH | Mir-Z03_S01_E06_G2 OH |
Z02_S01_E07 Mir-SHDW_B_01 | Mir-SHDW_B_02 | Z01_S01_E09_G1 OH | Mir-Z01_S01_E09_G1 OH | Z01_S01_E09_G2 OH | Mir-Z01_S01_E09_G2 OH | Z03_S01_E06_G1 OH | Mir-Z03_S01_E06_G1 OH | Z03_S01_E06_G2 OH | Mir-Z03_S01_E06_G2 OH | Z01_S01_E07 | Z01_S01_E08 |
Z03_S01_E06 Z01_S01_E09_G1 OH | Mir-Z01_S01_E09_G1 OH | Z01_S01_E09_G2 OH | Mir-Z01_S01_E09_G2 OH | Z02_S01_E06_G1 OH | Mir-Z02_S01_E06_G1 OH | Z03_S01_E06_G1 OH | Mir-Z03_S01_E06_G1 OH | Z03_S01_E06_G2 OH | Mir-Z03_S01_E06_G2 OH |
Z04_S01_E02 Mir-SHDW_B_01 | Mir-SHDW_B_02 | Z01_S01_E09_G1 OH | Z01_S01_E09_G2 OH | Z02_S01_E06_G1 OH | Z03_S01_E06_G1 OH | Z03_S01_E06_G2 OH | Z01_S01_E07 | Z01_S01_E08 | Z02_S01_E07 |
Z05_S01_E02 Mir-SHDW_B_01 | Mir-SHDW_B_02 | Z01_S01_E09_G1 OH | Z01_S01_E09_G2 OH | Z02_S01_E06_G1 OH | Z03_S01_E06_G1 OH | Z03_S01_E06_G2 OH | Z01_S01_E07 | Z01_S01_E08 | Z02_S01_E04 | Z02_S01_E05 | Z08_S01_E04 | Z09_S02_E02 |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
Z01_S01_E07 Z01_S01_E07_G1 |
Z01_S01_E09 Z01_S01_E09_G1 | Z01_S01_E09_G2 |
Z02_S01_E06 Z02_S01_E06_G1 |
Z02_S01_E07 Z02_S01_E07_G1 |
Z03_S01_E04 Z03_S01_E04_G1 | Z03_S02_E03_G1 |
Z03_S01_E06 Z03_S01_E06_G1 | Z03_S01_E06_G2 |
Z08_S01_E03 Z08_S01_E03_G1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Version

Version ID
1 23.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 4 15


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes No No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 4 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 1.000 1.000


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 17.10 17.10 17.10 17.10 17.10 17.10 17.10 17.10 17.10 17.10 17.10 17.10


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 17.06 17.06 17.06 17.06 17.06 17.06 17.06 17.06 17.06 17.06 17.06 17.06


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 B3_peninsula - ESP CTE_DB_HE WMO#= 40.68 -4.13 1.00 667.00 93565 1.1121


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Schedule SCHED22_WATER_MAINS_TEMP 0.00 0.00 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 Local comercial - Guía de aplicación DB HE 2019. EJEMPLOS (IV) 0.000 Country 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Algorithm {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
Space Heat Balance Sizing

Space Heat Balance Simulation

1 ThirdOrderBackwardDifference No No


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.140 270.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 LowerLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 4 10


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 9 126 10


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 Z01_RECEPCION_CAFETERIA 0.0 0.00 0.00 0.00 -0.85 -1.84 1.19 1 1 1 -5.11 24.65 -5.23 1.63 -9.93 3.43 3.43 164.65 TARP DOE-2 48.00 41.03 21.08 17.95 15 3 4 Yes
2 Z02_OFICINA 0.0 0.00 0.00 0.00 -4.75 -2.96 0.37 1 1 1 -7.57 14.60 -5.23 0.00 -10.93 3.43 3.43 20.23 TARP DOE-2 5.90 25.83 18.02 7.03 13 2 2 Yes
3 Z03_SALAS_DEPORTIVAS 0.0 0.00 0.00 0.00 3.53 0.67 1.30 1 1 1 -5.11 31.84 -5.23 5.23 -9.93 3.43 3.43 321.26 TARP DOE-2 93.66 124.54 95.20 25.96 12 4 4 Yes
4 Z04_ZONAS_SECAS_P_1 0.0 0.00 0.00 0.00 -2.33 -2.47 -2.03 1 1 1 -7.36 6.06 -4.85 0.00 -9.93 0.00 3.03 106.77 TARP DOE-2 35.26 27.98 27.98 0.00 17 0 0 Yes
5 Z05_VESTUARIOS_P_1 0.0 0.00 0.00 0.00 -2.27 -2.41 -1.97 1 1 1 -9.85 5.08 -4.85 0.00 -8.93 0.00 3.01 69.18 TARP DOE-2 22.97 45.50 45.50 0.00 18 0 0 Yes
6 Z06_ASEO_1 0.0 0.00 0.00 0.00 -5.94 -3.86 -2.22 1 1 1 -7.45 2.23 -4.85 0.00 -8.93 0.00 3.03 10.96 TARP DOE-2 3.62 1.27 1.27 0.00 8 0 0 Yes
7 Z07_ASEO_2 0.0 0.00 0.00 0.00 1.48 -3.86 -2.19 1 1 1 0.00 2.67 -4.85 0.00 -8.93 0.00 3.03 10.71 TARP DOE-2 3.53 1.31 1.31 0.00 8 0 0 Yes
8 Z08_ASEO_ACCESIBLE 0.0 0.00 0.00 0.00 -6.08 2.46 1.61 1 1 1 -7.19 2.70 0.00 5.23 -7.93 3.43 3.43 33.00 TARP DOE-2 9.62 24.23 23.53 0.60 8 1 0 Yes
9 Z09_ASCENSOR 0.0 0.00 0.00 0.00 -6.25 -0.95 -5.20E-002 1 1 1 -7.45 -5.11 -1.88 1.15E-002 -3.50 3.43 6.31 22.67 TARP DOE-2 3.59 12.23 12.23 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 Z01_RECEPCION_CAFETERIA 48.00 3.0 16.001 6.250E-002 3.250 0.000 0.000 3.000 0.000 0.000 6.250 No
2 Z02_OFICINA 5.90 1.0 5.899 0.170 4.408 0.000 0.000 3.000 0.000 0.000 7.408 No
3 Z03_SALAS_DEPORTIVAS 93.66 20.0 4.683 0.214 4.164 0.000 0.000 1.000 0.000 0.000 5.164 No
4 Z04_ZONAS_SECAS_P_1 35.26 2.0 17.629 5.672E-002 2.212 0.000 0.000 0.242 0.000 0.000 2.455 No
5 Z05_VESTUARIOS_P_1 22.97 0.0 N/A 0.000 0.849 0.000 0.000 0.000 0.000 0.000 0.849 No
6 Z06_ASEO_1 3.62 0.0 N/A 0.000 1.245 0.000 0.000 0.000 0.000 0.000 1.245 No
7 Z07_ASEO_2 3.53 0.0 N/A 0.000 1.273 0.000 0.000 0.000 0.000 0.000 1.273 No
8 Z08_ASEO_ACCESIBLE 9.62 0.0 N/A 0.000 1.299 0.000 0.000 0.000 0.000 0.000 1.299 No
9 Z09_ASCENSOR 3.59 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 Z01_RECEPCION_CAFETERIA_IG1 PEOPLE SCHED4 Z01_RECEPCION_CAFETERIA 48.00 3.0 3.0 6.250E-002 16.001 0.600 0.400 AutoCalculate Z01_RECEPCION_CAFETERIA_IG1 ACTIVITYLEVEL No 0.0000 0 3
2 Z02_OFICINA_IG1 PEOPLE SCHED11 Z02_OFICINA 5.90 1.0 1.0 0.170 5.899 0.700 0.300 AutoCalculate Z02_OFICINA_IG1 ACTIVITYLEVEL No 0.0000 0 1
3 Z03_SALAS_DEPORTIVAS_IG1 PEOPLE SCHED14 Z03_SALAS_DEPORTIVAS 93.66 20.0 20.0 0.214 4.683 0.200 0.800 AutoCalculate Z03_SALAS_DEPORTIVAS_IG1 ACTIVITYLEVEL No 0.0000 0 20
4 Z04_ZONAS_SECAS_P_1_IG1 PEOPLE SCHED19 Z04_ZONAS_SECAS_P_1 35.26 2.0 2.0 5.672E-002 17.629 0.600 0.400 AutoCalculate Z04_ZONAS_SECAS_P_1_IG1 ACTIVITYLEVEL No 0.0000 0 2


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 Z01_RECEPCION_CAFETERIA_IG2 LIGHTS SCHED5 Z01_RECEPCION_CAFETERIA 48.00 3.0 155.999 3.250 52.000 0.000 0.656 0.180 0.164 0.000 1 0.000 155.999
2 Z02_OFICINA_IG2 LIGHTS SCHED12 Z02_OFICINA 5.90 1.0 26.001 4.408 26.001 0.000 0.656 0.180 0.164 0.000 1 0.000 26.001
3 Z03_SALAS_DEPORTIVAS_IG2 LIGHTS SCHED15 Z03_SALAS_DEPORTIVAS 93.66 20.0 260.000 2.776 13.000 0.000 0.656 0.180 0.164 0.000 1 0.000 260.000
4 Z03_SALAS_DEPORTIVAS_IG3 LIGHTS SCHED15 Z03_SALAS_DEPORTIVAS 93.66 20.0 130.000 1.388 6.500 0.000 0.656 0.180 0.164 0.000 1 0.000 130.000
5 Z04_ZONAS_SECAS_P_1_IG2 LIGHTS SCHED19 Z04_ZONAS_SECAS_P_1 35.26 2.0 13.000 0.369 6.500 0.000 0.656 0.180 0.164 0.000 1 0.000 13.000
6 Z04_ZONAS_SECAS_P_1_IG3 LIGHTS SCHED20 Z04_ZONAS_SECAS_P_1 35.26 2.0 52.000 1.475 26.000 0.000 0.656 0.180 0.164 0.000 1 0.000 26.000
7 Z04_ZONAS_SECAS_P_1_IG4 LIGHTS SCHED19 Z04_ZONAS_SECAS_P_1 35.26 2.0 13.000 0.369 6.500 0.000 0.656 0.180 0.164 0.000 1 0.000 13.000
8 Z05_VESTUARIOS_P_1_IG1 LIGHTS SCHED7 Z05_VESTUARIOS_P_1 22.97 0.0 19.500 0.849 N/A 0.000 0.656 0.180 0.164 0.000 1 0.000 19.500
9 Z06_ASEO_1_IG1 LIGHTS SCHED21 Z06_ASEO_1 3.62 0.0 4.500 1.245 N/A 0.000 0.656 0.180 0.164 0.000 1 0.000 1.125
10 Z07_ASEO_2_IG1 LIGHTS SCHED21 Z07_ASEO_2 3.53 0.0 4.500 1.273 N/A 0.000 0.656 0.180 0.164 0.000 1 0.000 1.125
11 Z08_ASEO_ACCESIBLE_IG1 LIGHTS SCHED21 Z08_ASEO_ACCESIBLE 9.62 0.0 12.499 1.299 N/A 0.000 0.656 0.180 0.164 0.000 1 0.000 3.125


OtherEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 Z01_RECEPCION_CAFETERIA_IG3 ELECEQ SCHED6 Z01_RECEPCION_CAFETERIA 48.00 3.0 144.006 3.000 48.002 0.000 0.700 0.000 0.300 0.000 144.006
2 Z02_OFICINA_IG3 ELECEQ SCHED13 Z02_OFICINA 5.90 1.0 17.697 3.000 17.697 0.000 0.700 0.000 0.300 0.000 17.697
3 Z03_SALAS_DEPORTIVAS_IG4 ELECEQ SCHED16 Z03_SALAS_DEPORTIVAS 93.66 20.0 93.659 1.000 4.683 0.000 0.700 0.000 0.300 0.000 93.659
4 Z04_ZONAS_SECAS_P_1_IG5 ELECEQ SCHED19 Z04_ZONAS_SECAS_P_1 35.26 2.0 8.545 0.242 4.272 0.000 0.700 0.000 0.300 0.000 8.545


Solar View Factor Check Values

Zone/Enclosure Name Original Check Value Calculated Fixed Check Value Final Check Value Number of Iterations Fixed RowSum Convergence Used RowSum Convergence
1 Z01_RECEPCION_CAFETERIA 3.552714E-015 6.709350E-004 6.709350E-004 12 6.709350E-004 6.709350E-004
2 Z02_OFICINA 7.105427E-015 9.655025E-004 9.655025E-004 12 9.655025E-004 9.655025E-004
3 Z03_SALAS_DEPORTIVAS 3.552714E-015 8.882460E-004 8.882460E-004 12 8.882460E-004 8.882460E-004
4 Z04_ZONAS_SECAS_P_1 0.000000 9.567066E-004 9.567066E-004 10 9.567066E-004 9.567066E-004
5 Z05_VESTUARIOS_P_1 1.776357E-014 8.003999E-004 8.003999E-004 8 8.003999E-004 8.003999E-004
6 Z06_ASEO_1 0.000000 7.208172E-004 7.208172E-004 11 7.208172E-004 7.208172E-004
7 Z07_ASEO_2 3.552714E-015 6.927155E-004 6.927155E-004 11 6.927155E-004 6.927155E-004
8 Z08_ASEO_ACCESIBLE 0.000000 7.480596E-004 7.480596E-004 11 7.480596E-004 7.480596E-004
9 Z09_ASCENSOR 3.552714E-015 9.294728E-004 9.294728E-004 8 9.294728E-004 9.294728E-004


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Surface View Factor Check Values

Zone/Enclosure Name Original Check Value Calculated Fixed Check Value Final Check Value Number of Iterations Fixed RowSum Convergence Used RowSum Convergence
1 Z01_RECEPCION_CAFETERIA 3.552714E-015 6.709350E-004 6.709350E-004 12 6.709350E-004 6.709350E-004
2 Z02_OFICINA 7.105427E-015 9.655025E-004 9.655025E-004 12 9.655025E-004 9.655025E-004
3 Z03_SALAS_DEPORTIVAS 3.552714E-015 8.882460E-004 8.882460E-004 12 8.882460E-004 8.882460E-004
4 Z04_ZONAS_SECAS_P_1 0.000000 9.567066E-004 9.567066E-004 10 9.567066E-004 9.567066E-004
5 Z05_VESTUARIOS_P_1 1.776357E-014 8.003999E-004 8.003999E-004 8 8.003999E-004 8.003999E-004
6 Z06_ASEO_1 0.000000 7.208172E-004 7.208172E-004 11 7.208172E-004 7.208172E-004
7 Z07_ASEO_2 3.552714E-015 6.927155E-004 6.927155E-004 11 6.927155E-004 6.927155E-004
8 Z08_ASEO_ACCESIBLE 0.000000 7.480596E-004 7.480596E-004 11 7.480596E-004 7.480596E-004
9 Z09_ASCENSOR 3.552714E-015 9.294728E-004 9.294728E-004 8 9.294728E-004 9.294728E-004


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 Z01_S01_E07 2 96.37 107.48 14.36 2 3.43 9.63 2.62 0.44 4 No No
2 Z01_S01_E07_G1 2 96.37 107.48 14.36 2 3.43 9.63 2.62 0.44 2 No No
3 Z01_S01_E08 2 50.44 41.51 6.93 2 3.43 9.63 2.62 0.44 4 No No
4 Z01_S01_E09 2 96.37 107.48 14.36 2 3.43 9.63 2.62 0.44 4 No No
5 Z01_S01_E09_G1 2 96.37 107.48 14.36 2 3.43 9.63 2.62 0.44 2 No No
6 Z01_S01_E09_G2 2 96.37 107.48 14.36 2 3.43 9.63 2.62 0.44 2 No No
7 Z01_S01_E10 1 0.00 0.00 0.00 1 3.43 9.63 2.62 0.44 0 No No
8 Z01_S01_E11 1 0.00 0.00 0.00 1 3.43 9.63 2.62 0.44 0 No No
9 Z01_S01_E12 1 0.00 0.00 0.00 1 3.43 9.63 2.62 0.44 0 No No
10 Z01_S01_E13 1 0.00 0.00 0.00 1 3.43 9.63 2.62 0.44 0 No No
11 Z01_S01_E14 1 0.00 0.00 0.00 1 3.43 9.63 2.62 0.44 0 No No
12 Z01_S01_E07_G1_TB2_LATERALES V 2 96.37 107.48 14.36 2 3.43 9.63 2.62 0.44 3 No No
13 Z01_S01_TB09 FF 2 96.37 107.48 14.36 2 3.43 9.63 2.62 0.44 3 No No
14 Z01_S01_TB45 P 2 96.37 107.48 14.36 2 3.43 9.63 2.62 0.44 3 No No
15 Z01_S01_E01 1 0.00 0.00 0.00 1 3.43 9.63 2.62 0.44 0 No No
16 Z01_S01_E03 2 10.97 18.30 0.00 2 3.43 9.63 2.62 0.44 0 No No
17 Z01_S01_E05 1 0.00 0.00 0.00 1 3.43 9.63 2.62 0.44 0 No No
18 Z01_S01_E06 1 0.00 0.00 0.00 1 3.43 9.63 2.62 0.44 0 No No
19 Z01_RECEPCION_CAFETERIA FURNITURE 1 0.00 0.00 0.00 1 3.43 9.63 2.62 0.44 0 No No
20 Z02_S01_E04 2 50.44 41.51 6.93 2 3.43 6.77 0.43 0.27 4 No No
21 Z02_S01_E05 2 50.44 41.51 6.93 2 3.43 6.77 0.43 0.27 4 No No
22 Z02_S01_E06 2 96.37 107.48 14.36 2 3.43 6.77 0.43 0.27 4 No No
23 Z02_S01_E06_G1 2 96.37 107.48 14.36 2 3.43 6.77 0.43 0.27 2 No No
24 Z02_S01_E07 2 49.71 49.63 6.93 2 3.43 6.77 0.43 0.27 4 No No
25 Z02_S01_E07_G1 2 49.71 49.63 6.93 2 3.43 6.77 0.43 0.27 2 No No
26 Z02_S01_E09 1 0.00 0.00 0.00 1 3.43 6.77 0.43 0.27 0 No No
27 Z02_S01_E06_G1_TB2_LATERALES V 2 96.37 107.48 14.36 2 3.43 6.77 0.43 0.27 3 No No
28 Z02_S01_TB06 FC 2 96.37 107.48 14.36 2 3.43 6.77 0.43 0.27 3 No No
29 Z02_S01_TB10 FF 2 96.37 107.48 14.36 2 3.43 6.77 0.43 0.27 3 No No
30 Z02_S01_TB23 P 2 96.37 107.48 14.36 2 3.43 6.77 0.43 0.27 3 No No
31 iz-Z01_S01_E10 1 0.00 0.00 0.00 1 3.43 6.77 0.43 0.27 0 No No
32 Z02_S01_E01 1 0.00 0.00 0.00 1 3.43 6.77 0.43 0.27 0 No No
33 Z02_S01_E02 1 0.00 0.00 0.00 1 3.43 6.77 0.43 0.27 0 No No
34 Z02_S01_E03 1 0.00 0.00 0.00 1 3.43 6.77 0.43 0.27 0 No No
35 Z02_OFICINA FURNITURE 1 0.00 0.00 0.00 1 3.43 6.77 0.43 0.27 0 No No
36 Z03_S01_E04 2 101.12 54.66 6.93 2 3.43 32.72 3.95 0.21 3 No No
37 Z03_S01_E04_G1 2 101.12 54.66 6.93 2 3.43 32.72 3.95 0.21 2 No No
38 Z03_S02_E03_G1 2 101.12 54.66 6.93 2 3.43 32.72 3.95 0.21 2 No No
39 Z03_S01_E05 2 49.71 49.63 6.93 2 3.43 32.72 3.95 0.21 4 No No
40 Z03_S01_E06 2 96.37 107.48 14.36 2 3.43 32.72 3.95 0.21 4 No No
41 Z03_S01_E06_G1 2 96.37 107.48 14.36 2 3.43 32.72 3.95 0.21 2 No No
42 Z03_S01_E06_G2 2 96.37 107.48 14.36 2 3.43 32.72 3.95 0.21 2 No No
43 Z03_S02_E04 1 0.00 0.00 0.00 1 3.43 32.72 3.95 0.21 0 No No
44 Z03_S01_E04_G1_TB2_LATERALES V 2 96.37 107.48 14.36 2 3.43 32.72 3.95 0.21 3 No No
45 Z03_S01_TB09 FF 2 96.37 107.48 14.36 2 3.43 32.72 3.95 0.21 3 No No
46 Z03_S01_TB23 P 2 96.37 107.48 14.36 2 3.43 32.72 3.95 0.21 3 No No
47 iz-Z01_S01_E13 1 0.00 0.00 0.00 1 3.43 32.72 3.95 0.21 0 No No
48 iz-Z01_S01_E14 1 0.00 0.00 0.00 1 3.43 32.72 3.95 0.21 0 No No
49 Z03_S01_E01 1 0.00 0.00 0.00 1 3.43 32.72 3.95 0.21 0 No No
50 Z03_S01_E02 2 80.47 49.33 0.00 2 3.43 32.72 3.95 0.21 0 No No
51 Z03_S01_E03 1 0.00 0.00 0.00 1 3.43 32.72 3.95 0.21 0 No No
52 Z03_SALAS_DEPORTIVAS FURNITURE 1 0.00 0.00 0.00 1 3.43 32.72 3.95 0.21 0 No No
53 Z03_S01_E08 FURNITURE 1 0.00 0.00 0.00 1 3.43 32.72 3.95 0.21 0 No No
54 Z04_S01_E04 2 0.00 0.00 0.00 2 3.03 8.69 3.86 0.00 0 No No
55 Z04_S01_E06 1 0.00 0.00 0.00 1 3.03 8.69 3.86 0.00 0 No No
56 Z04_S02_E04 2 101.12 54.66 6.93 2 3.03 8.69 3.86 0.00 0 No No
57 Z04_S02_E05 1 0.00 0.00 0.00 1 3.03 8.69 3.86 0.00 0 No No
58 Z04_S02_E06 1 0.00 0.00 0.00 1 3.03 8.69 3.86 0.00 0 No No
59 Z04_S02_E07 1 0.00 0.00 0.00 1 3.03 8.69 3.86 0.00 0 No No
60 Z04_S02_E10 1 0.00 0.00 0.00 1 3.03 8.69 3.86 0.00 0 No No
61 Z04_S02_E11 1 0.00 0.00 0.00 1 3.03 8.69 3.86 0.00 0 No No
62 Z04_S02_E12 1 0.00 0.00 0.00 1 3.03 8.69 3.86 0.00 0 No No
63 Z04_S03_E05 1 0.00 0.00 0.00 1 3.03 8.69 3.86 0.00 0 No No
64 Z04_S01_TB03 FS 2 96.37 107.48 14.36 2 3.03 8.69 3.86 0.00 0 No No
65 Z04_S01_TB04 FF 2 96.37 107.48 14.36 2 3.03 8.69 3.86 0.00 0 No No
66 Z04_S01_TB05 FC 2 96.37 107.48 14.36 2 3.03 8.69 3.86 0.00 0 No No
67 Z04_S01_E01 2 0.00 0.00 0.00 2 3.03 8.69 3.86 0.00 0 No No
68 Z04_S01_E02 2 12.01 22.93 0.00 2 3.03 8.69 3.86 0.00 0 No No
69 iz-Z01_S01_E01 1 0.00 0.00 0.00 1 3.03 8.69 3.86 0.00 0 No No
70 iz-Z02_S01_E02 1 0.00 0.00 0.00 1 3.03 8.69 3.86 0.00 0 No No
71 Z04_ZONAS_SECAS_P_1 FURNITURE 1 0.00 0.00 0.00 1 3.03 8.69 3.86 0.00 0 No No
72 Z04_S01_E05 FURNITURE 1 0.00 0.00 0.00 1 3.03 8.69 3.86 0.00 0 No No
73 Z05_S01_E04 2 0.00 0.00 0.00 2 3.01 13.97 2.32 0.00 0 No No
74 Z05_S01_E05 2 50.44 41.51 6.93 2 3.01 13.97 2.32 0.00 0 No No
75 Z05_S01_E06 2 101.12 54.66 6.93 2 3.01 13.97 2.32 0.00 0 No No
76 Z05_S01_E07 1 0.00 0.00 0.00 1 3.01 13.97 2.32 0.00 0 No No
77 Z05_S01_E09 1 0.00 0.00 0.00 1 3.01 13.97 2.32 0.00 0 No No
78 Z05_S02_E03 2 0.00 0.00 0.00 2 3.01 13.97 2.32 0.00 0 No No
79 Z05_S02_E04 2 101.12 54.66 6.93 2 3.01 13.97 2.32 0.00 0 No No
80 Z05_S02_E05 2 49.71 49.63 6.93 2 3.01 13.97 2.32 0.00 0 No No
81 Z05_S02_E06 1 0.00 0.00 0.00 1 3.01 13.97 2.32 0.00 0 No No
82 Z05_S01_TB03 FS 2 96.37 107.48 14.36 2 3.01 13.97 2.32 0.00 0 No No
83 Z05_S02_TB04 FF 2 96.37 107.48 14.36 2 3.01 13.97 2.32 0.00 0 No No
84 iz-Z04_S02_E05 1 0.00 0.00 0.00 1 3.01 13.97 2.32 0.00 0 No No
85 iz-Z04_S02_E06 1 0.00 0.00 0.00 1 3.01 13.97 2.32 0.00 0 No No
86 Z05_S01_E01 2 0.00 0.00 0.00 2 3.01 13.97 2.32 0.00 0 No No
87 Z05_S02_E01 2 0.00 0.00 0.00 2 3.01 13.97 2.32 0.00 0 No No
88 Z05_S01_E02 2 12.01 22.93 0.00 2 3.01 13.97 2.32 0.00 0 No No
89 Z05_S01_E03 2 12.01 22.93 0.00 2 3.01 13.97 2.32 0.00 0 No No
90 iz-Z03_S01_E01 1 0.00 0.00 0.00 1 3.01 13.97 2.32 0.00 0 No No
91 Z05_VESTUARIOS_P_1 FURNITURE 1 0.00 0.00 0.00 1 3.01 13.97 2.32 0.00 0 No No
92 Z06_S01_E03 2 0.00 0.00 0.00 2 3.03 0.60 0.50 0.00 0 No No
93 Z06_S01_TB03 FS 2 96.37 107.48 14.36 2 3.03 0.60 0.50 0.00 0 No No
94 Z06_S01_TB04 FF 2 96.37 107.48 14.36 2 3.03 0.60 0.50 0.00 0 No No
95 iz-Z04_S01_E06 1 0.00 0.00 0.00 1 3.03 0.60 0.50 0.00 0 No No
96 iz-Z04_S02_E07 1 0.00 0.00 0.00 1 3.03 0.60 0.50 0.00 0 No No
97 iz-Z05_S01_E07 1 0.00 0.00 0.00 1 3.03 0.60 0.50 0.00 0 No No
98 Z06_S01_E01 2 0.00 0.00 0.00 2 3.03 0.60 0.50 0.00 0 No No
99 iz-Z02_S01_E01 1 0.00 0.00 0.00 1 3.03 0.60 0.50 0.00 0 No No
100 Z07_S01_E03 2 0.00 0.00 0.00 2 3.03 0.60 0.94 0.00 0 No No
101 Z07_S01_TB03 FS 2 96.37 107.48 14.36 2 3.03 0.60 0.94 0.00 0 No No
102 Z07_S01_TB04 FF 2 96.37 107.48 14.36 2 3.03 0.60 0.94 0.00 0 No No
103 iz-Z04_S02_E10 1 0.00 0.00 0.00 1 3.03 0.60 0.94 0.00 0 No No
104 iz-Z04_S03_E05 1 0.00 0.00 0.00 1 3.03 0.60 0.94 0.00 0 No No
105 iz-Z05_S02_E06 1 0.00 0.00 0.00 1 3.03 0.60 0.94 0.00 0 No No
106 Z07_S01_E01 2 0.00 0.00 0.00 2 3.03 0.60 0.94 0.00 0 No No
107 iz-Z01_S01_E05 1 0.00 0.00 0.00 1 3.03 0.60 0.94 0.00 0 No No
108 Z08_S01_E03 2 101.12 54.66 6.93 2 3.43 7.13 1.27 2.46E-002 3 No No
109 Z08_S01_E03_G1 2 101.12 54.66 6.93 2 3.43 7.13 1.27 2.46E-002 2 No No
110 Z08_S01_E04 2 50.44 41.51 6.93 2 3.43 7.13 1.27 2.46E-002 4 No No
111 Z08_S01_E07 1 0.00 0.00 0.00 1 3.43 7.13 1.27 2.46E-002 0 No No
112 Z08_S01_E03_G1_TB2_LATERALES V 2 96.37 107.48 14.36 2 3.43 7.13 1.27 2.46E-002 3 No No
113 iz-Z01_S01_E12 1 0.00 0.00 0.00 1 3.43 7.13 1.27 2.46E-002 0 No No
114 iz-Z03_S02_E04 1 0.00 0.00 0.00 1 3.43 7.13 1.27 2.46E-002 0 No No
115 Z08_S01_E01 2 9.23 13.27 0.00 2 3.43 7.13 1.27 2.46E-002 0 No No
116 Z08_S01_E02 1 0.00 0.00 0.00 1 3.43 7.13 1.27 2.46E-002 0 No No
117 Z09_S01_E02 2 101.12 54.66 6.93 2 6.31 3.81 1.70 0.00 0 No No
118 Z09_S02_E02 2 50.44 41.51 6.93 2 6.31 3.81 1.70 0.00 0 No No
119 iz-Z01_S01_E11 1 0.00 0.00 0.00 1 6.31 3.81 1.70 0.00 0 No No
120 iz-Z02_S01_E09 1 0.00 0.00 0.00 1 6.31 3.81 1.70 0.00 0 No No
121 iz-Z04_S02_E11 1 0.00 0.00 0.00 1 6.31 3.81 1.70 0.00 0 No No
122 iz-Z04_S02_E12 1 0.00 0.00 0.00 1 6.31 3.81 1.70 0.00 0 No No
123 iz-Z05_S01_E09 1 0.00 0.00 0.00 1 6.31 3.81 1.70 0.00 0 No No
124 iz-Z08_S01_E07 1 0.00 0.00 0.00 1 6.31 3.81 1.70 0.00 0 No No
125 Z09_S01_E01 2 0.00 0.00 0.00 2 6.31 3.81 1.70 0.00 0 No No
126 Z09_S02_E01 1 0.00 0.00 0.00 1 6.31 3.81 1.70 0.00 0 No No


Building Convection Parameters:North Facade

Perimeter Height Xmin Xmax Ymin Ymax Zmin Zmax
1 54.66 6.93 -9.85 9.85 -7.25E-002 5.23 -3.50 3.43


Building Convection Parameters:Northeast Facade

Perimeter Height Xmin Xmax Ymin Ymax Zmin Zmax
1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Building Convection Parameters:East Facade

Perimeter Height Xmin Xmax Ymin Ymax Zmin Zmax
1 49.63 6.93 -5.17 9.85 -4.85 4.85 -3.50 3.43


Building Convection Parameters:Southeast Facade

Perimeter Height Xmin Xmax Ymin Ymax Zmin Zmax
1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Building Convection Parameters:South Facade

Perimeter Height Xmin Xmax Ymin Ymax Zmin Zmax
1 107.48 14.36 -7.19 31.84 -5.23 0.00 -10.93 3.43


Building Convection Parameters:Southwest Facade

Perimeter Height Xmin Xmax Ymin Ymax Zmin Zmax
1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Building Convection Parameters:West Facade

Perimeter Height Xmin Xmax Ymin Ymax Zmin Zmax
1 41.51 6.93 -9.85 0.00 -4.85 4.85 -3.50 3.43


Building Convection Parameters:Roof

Area [m2] Perimeter [m] Height [m] Tilt [deg] Azimuth [deg]
1 12.01 22.93 0.00 0.00 180.00! <ZoneInfiltration Airflow Stats Nominal>


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 Z01_RECEPCION_CAFETERIA Mixing/Well-Stirred
2 Z02_OFICINA Mixing/Well-Stirred
3 Z03_SALAS_DEPORTIVAS Mixing/Well-Stirred
4 Z04_ZONAS_SECAS_P_1 Mixing/Well-Stirred
5 Z05_VESTUARIOS_P_1 Mixing/Well-Stirred
6 Z06_ASEO_1 Mixing/Well-Stirred
7 Z07_ASEO_2 Mixing/Well-Stirred
8 Z08_ASEO_ACCESIBLE Mixing/Well-Stirred
9 Z09_ASCENSOR Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 4


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 Z01_RECEPCION_CAFETERIA Cooling 1415.94224 1415.94224 0.10235 0.10235 WINTER 1/13 15:00:00 11.40000 5.00494E-003 48.00200 3.00000 2.40000E-002 0.00000
2 Z01_RECEPCION_CAFETERIA Heating 0.00000 0.00000 0.00000 2.40000E-002   00:15:00 28.02500 1.04615E-002 48.00200 3.00000 2.40000E-002 0.00000
3 Z02_OFICINA Cooling 377.09574 377.09574 2.72596E-002 2.72596E-002 SUMMER 7/22 14:00:00 34.30000 9.78863E-003 5.89900 1.00000 1.25000E-002 0.00000
4 Z02_OFICINA Heating 12.60168 12.60168 3.57943E-004 1.25000E-002 WINTER 1/9 09:15:00 6.35000 5.02482E-003 5.89900 1.00000 1.25000E-002 0.00000
5 Z03_SALAS_DEPORTIVAS Cooling 2577.89515 2577.89515 0.18640 0.18640 SUMMER 7/22 20:00:00 31.60000 1.07482E-002 93.65900 20.00000 0.16000 0.00000
6 Z03_SALAS_DEPORTIVAS Heating 0.00000 0.00000 0.00000 0.16000   00:15:00 28.02500 1.04615E-002 93.65900 20.00000 0.16000 0.00000
7 Z04_ZONAS_SECAS_P_1 Cooling 3.95611 3.95611 2.85984E-004 3.06920E-002 SUMMER 7/23 19:00:00 30.90000 1.06055E-002 35.25800 2.00000 3.06920E-002 0.00000
8 Z04_ZONAS_SECAS_P_1 Heating 347.33782 347.33782 1.01571E-002 3.06920E-002 WINTER 1/13 09:00:00 4.80000 4.41475E-003 35.25800 2.00000 3.06920E-002 0.00000
9 Z05_VESTUARIOS_P_1 Cooling 0.00000 0.00000 0.00000 1.26323E-002 SUMMER 7/22 22:00:00 29.70000 1.09492E-002 22.96800 0.00000 1.26323E-002 0.00000
10 Z05_VESTUARIOS_P_1 Heating 638.42971 638.42971 1.85490E-002 1.85490E-002 WINTER 1/13 09:00:00 4.80000 4.41475E-003 22.96800 0.00000 1.26323E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR Cooling Sensible 584.66 0.10235 2.40000E-002 SUMMER 7/22 00:00:00
2 LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR Heating Sensible 0.00 2.40000E-002 2.40000E-002 WINTER 1/12 08:00:00
3 LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR Cooling Sensible 300.32 2.72596E-002 1.25000E-002 SUMMER 7/22 00:00:00
4 LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR Heating Sensible 81.72 1.25000E-002 1.25000E-002 WINTER 1/12 08:00:00
5 LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR Cooling Sensible 3361.36 0.18640 0.16000 SUMMER 7/27 00:00:00
6 LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR Heating Sensible 0.00 0.16000 0.16000 WINTER 1/12 08:00:00
7 LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR Cooling Sensible 620.79 3.06920E-002 3.06920E-002 SUMMER 7/22 00:00:00
8 LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR Heating Sensible 253.80 3.06920E-002 3.06920E-002 WINTER 1/12 08:00:00
9 LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR Cooling Sensible 238.57 1.26323E-002 1.26323E-002 SUMMER 7/22 00:00:00
10 LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR Heating Sensible 104.46 1.85490E-002 1.26323E-002 WINTER 1/13 09:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat UT1_ZONE1_RECUPERACION_DE_CALOR Design Size Maximum Air Flow Rate [m3/s] 0.02400
2 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS Design Size Cooling Supply Air Flow Rate [m3/s] 0.10235
3 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS Design Size Heating Supply Air Flow Rate [m3/s] 0.10235
4 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS Design Size No Cooling Supply Air Flow Rate [m3/s] 0.10235
5 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS Design Size No Heating Supply Air Flow Rate [m3/s] 0.10235
6 Fan:OnOff UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.10235
7 Coil:Cooling:DX:VariableRefrigerantFlow UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.10235
8 Coil:Cooling:DX:VariableRefrigerantFlow UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 1694.23352
9 Coil:Cooling:DX:VariableRefrigerantFlow UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
10 Coil:Heating:DX:VariableRefrigerantFlow UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.10235
11 Coil:Heating:DX:VariableRefrigerantFlow UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL Design Size Gross Rated Heating Capacity [W] 1694.23352
12 AirTerminal:SingleDuct:ConstantVolume:NoReheat UT1_ZONE2_RECUPERACION_DE_CALOR Design Size Maximum Air Flow Rate [m3/s] 0.01250
13 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS Design Size Cooling Supply Air Flow Rate [m3/s] 0.02726
14 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS Design Size Heating Supply Air Flow Rate [m3/s] 0.02726
15 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS Design Size No Cooling Supply Air Flow Rate [m3/s] 0.02726
16 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS Design Size No Heating Supply Air Flow Rate [m3/s] 0.02726
17 Fan:OnOff UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.02726
18 Coil:Cooling:DX:VariableRefrigerantFlow UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.02726
19 Coil:Cooling:DX:VariableRefrigerantFlow UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 451.24260
20 Coil:Cooling:DX:VariableRefrigerantFlow UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
21 Coil:Heating:DX:VariableRefrigerantFlow UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.02726
22 Coil:Heating:DX:VariableRefrigerantFlow UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL Design Size Gross Rated Heating Capacity [W] 451.24260
23 AirTerminal:SingleDuct:ConstantVolume:NoReheat UT1_ZONE3_RECUPERACION_DE_CALOR Design Size Maximum Air Flow Rate [m3/s] 0.16000
24 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS Design Size Cooling Supply Air Flow Rate [m3/s] 0.18640
25 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS Design Size Heating Supply Air Flow Rate [m3/s] 0.18640
26 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS Design Size No Cooling Supply Air Flow Rate [m3/s] 0.18640
27 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS Design Size No Heating Supply Air Flow Rate [m3/s] 0.18640
28 Fan:OnOff UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.18640
29 Coil:Cooling:DX:VariableRefrigerantFlow UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.18640
30 Coil:Cooling:DX:VariableRefrigerantFlow UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 3821.04563
31 Coil:Cooling:DX:VariableRefrigerantFlow UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.76690
32 Coil:Heating:DX:VariableRefrigerantFlow UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.18640
33 Coil:Heating:DX:VariableRefrigerantFlow UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL Design Size Gross Rated Heating Capacity [W] 3821.04563
34 AirTerminal:SingleDuct:ConstantVolume:NoReheat UT1_ZONE4_RECUPERACION_DE_CALOR Design Size Maximum Air Flow Rate [m3/s] 0.03069
35 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS Design Size Cooling Supply Air Flow Rate [m3/s] 0.03069
36 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS Design Size Heating Supply Air Flow Rate [m3/s] 0.03069
37 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS Design Size No Cooling Supply Air Flow Rate [m3/s] 0.03069
38 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS Design Size No Heating Supply Air Flow Rate [m3/s] 0.03069
39 Fan:OnOff UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.03069
40 Coil:Cooling:DX:VariableRefrigerantFlow UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.03069
41 Coil:Cooling:DX:VariableRefrigerantFlow UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 603.26547
42 Coil:Cooling:DX:VariableRefrigerantFlow UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.78263
43 Coil:Heating:DX:VariableRefrigerantFlow UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.03069
44 Coil:Heating:DX:VariableRefrigerantFlow UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL Design Size Gross Rated Heating Capacity [W] 603.26547
45 AirTerminal:SingleDuct:ConstantVolume:NoReheat UT1_ZONE5_RECUPERACION_DE_CALOR Design Size Maximum Air Flow Rate [m3/s] 0.01263
46 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS Design Size Cooling Supply Air Flow Rate [m3/s] 0.01855
47 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS Design Size Heating Supply Air Flow Rate [m3/s] 0.01855
48 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS Design Size No Cooling Supply Air Flow Rate [m3/s] 0.01855
49 ZoneHVAC:TerminalUnit:VariableRefrigerantFlow UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS Design Size No Heating Supply Air Flow Rate [m3/s] 0.01855
50 Fan:OnOff UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.01855
51 Coil:Cooling:DX:VariableRefrigerantFlow UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.01855
52 Coil:Cooling:DX:VariableRefrigerantFlow UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 307.05151
53 Coil:Cooling:DX:VariableRefrigerantFlow UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
54 Coil:Heating:DX:VariableRefrigerantFlow UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.01855
55 Coil:Heating:DX:VariableRefrigerantFlow UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS HEATING COIL Design Size Gross Rated Heating Capacity [W] 307.05151
56 AirConditioner:VariableRefrigerantFlow LOOP_VRF1_SYSTEM1_UNIDAD_EXTERIOR_DE_BOMBA_DE_CALOR_VRF Design Size Rated Total Cooling Capacity (gross) [W] 6876.83873
57 AirConditioner:VariableRefrigerantFlow LOOP_VRF1_SYSTEM1_UNIDAD_EXTERIOR_DE_BOMBA_DE_CALOR_VRF Design Size Rated Total Heating Capacity [W] 6876.83873
58 AirConditioner:VariableRefrigerantFlow LOOP_VRF1_SYSTEM1_UNIDAD_EXTERIOR_DE_BOMBA_DE_CALOR_VRF Design Size Resistive Defrost Heater Capacity [W] 0.00000
59 AirConditioner:VariableRefrigerantFlow LOOP_VRF1_SYSTEM1_UNIDAD_EXTERIOR_DE_BOMBA_DE_CALOR_VRF Design Size Evaporative Condenser Air Flow Rate [m3/s] 0.78396
60 ZoneHVAC:IdealLoadsAirSystem Z06_ASEO_1-UT1_ZONE6_IDEAL_LOADS_IDEALLOADSAIRSYSTEM User-Specified Maximum Heating Air Flow Rate [m3/s] 0.00000
61 ZoneHVAC:IdealLoadsAirSystem Z06_ASEO_1-UT1_ZONE6_IDEAL_LOADS_IDEALLOADSAIRSYSTEM User-Specified Maximum Cooling Air Flow Rate [m3/s] 0.00000
62 ZoneHVAC:IdealLoadsAirSystem Z07_ASEO_2-UT1_ZONE7_IDEAL_LOADS_IDEALLOADSAIRSYSTEM User-Specified Maximum Heating Air Flow Rate [m3/s] 0.00000
63 ZoneHVAC:IdealLoadsAirSystem Z07_ASEO_2-UT1_ZONE7_IDEAL_LOADS_IDEALLOADSAIRSYSTEM User-Specified Maximum Cooling Air Flow Rate [m3/s] 0.00000
64 ZoneHVAC:IdealLoadsAirSystem Z08_ASEO_ACCESIBLE-UT1_ZONE8_IDEAL_LOADS_IDEALLOADSAIRSYSTEM User-Specified Maximum Heating Air Flow Rate [m3/s] 0.00000
65 ZoneHVAC:IdealLoadsAirSystem Z08_ASEO_ACCESIBLE-UT1_ZONE8_IDEAL_LOADS_IDEALLOADSAIRSYSTEM User-Specified Maximum Cooling Air Flow Rate [m3/s] 0.00000
66 AirLoopHVAC LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.02400
67 AirLoopHVAC LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.02400
68 AirLoopHVAC LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR Sum of Air Terminal Maximum Flow Rates [m3/s] 0.02400
69 AirLoopHVAC LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR Adjusted Heating Design Air Flow Rate [m3/s] 0.02400
70 AirLoopHVAC LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR Adjusted Cooling Design Air Flow Rate [m3/s] 0.02400
71 AirLoopHVAC LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR Adjusted Main Design Air Flow Rate [m3/s] 0.02400
72 AirLoopHVAC LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR User Heating Air Flow Ratio [] 1.00000
73 AirLoopHVAC LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR Calculated Heating Air Flow Ratio [] 1.00000
74 AirLoopHVAC LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.01250
75 AirLoopHVAC LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.01250
76 AirLoopHVAC LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR Sum of Air Terminal Maximum Flow Rates [m3/s] 0.01250
77 AirLoopHVAC LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR Adjusted Heating Design Air Flow Rate [m3/s] 0.01250
78 AirLoopHVAC LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR Adjusted Cooling Design Air Flow Rate [m3/s] 0.01250
79 AirLoopHVAC LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR Adjusted Main Design Air Flow Rate [m3/s] 0.01250
80 AirLoopHVAC LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR User Heating Air Flow Ratio [] 1.00000
81 AirLoopHVAC LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR Calculated Heating Air Flow Ratio [] 1.00000
82 AirLoopHVAC LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.16000
83 AirLoopHVAC LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.16000
84 AirLoopHVAC LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR Sum of Air Terminal Maximum Flow Rates [m3/s] 0.16000
85 AirLoopHVAC LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR Adjusted Heating Design Air Flow Rate [m3/s] 0.16000
86 AirLoopHVAC LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR Adjusted Cooling Design Air Flow Rate [m3/s] 0.16000
87 AirLoopHVAC LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR Adjusted Main Design Air Flow Rate [m3/s] 0.16000
88 AirLoopHVAC LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR User Heating Air Flow Ratio [] 1.00000
89 AirLoopHVAC LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR Calculated Heating Air Flow Ratio [] 1.00000
90 AirLoopHVAC LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.03069
91 AirLoopHVAC LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.03069
92 AirLoopHVAC LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR Sum of Air Terminal Maximum Flow Rates [m3/s] 0.03069
93 AirLoopHVAC LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR Adjusted Heating Design Air Flow Rate [m3/s] 0.03069
94 AirLoopHVAC LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR Adjusted Cooling Design Air Flow Rate [m3/s] 0.03069
95 AirLoopHVAC LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR Adjusted Main Design Air Flow Rate [m3/s] 0.03069
96 AirLoopHVAC LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR User Heating Air Flow Ratio [] 1.00000
97 AirLoopHVAC LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR Calculated Heating Air Flow Ratio [] 1.00000
98 AirLoopHVAC LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.01263
99 AirLoopHVAC LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.01263
100 AirLoopHVAC LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR Sum of Air Terminal Maximum Flow Rates [m3/s] 0.01263
101 AirLoopHVAC LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR Adjusted Heating Design Air Flow Rate [m3/s] 0.01263
102 AirLoopHVAC LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR Adjusted Cooling Design Air Flow Rate [m3/s] 0.01263
103 AirLoopHVAC LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR Adjusted Main Design Air Flow Rate [m3/s] 0.01263
104 AirLoopHVAC LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR User Heating Air Flow Ratio [] 1.00000
105 AirLoopHVAC LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR Calculated Heating Air Flow Ratio [] 1.00000
106 AirLoopHVAC LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR Design Supply Air Flow Rate [m3/s] 0.02400
107 AirLoopHVAC LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR Design Supply Air Flow Rate [m3/s] 0.01250
108 AirLoopHVAC LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR Design Supply Air Flow Rate [m3/s] 0.16000
109 AirLoopHVAC LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR Design Supply Air Flow Rate [m3/s] 0.03069
110 AirLoopHVAC LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR Design Supply Air Flow Rate [m3/s] 0.01263
111 Controller:OutdoorAir LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR OA CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.02400
112 Controller:OutdoorAir LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR OA CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.02400
113 HeatExchanger:AirToAir:SensibleAndLatent LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 0.02400
114 Fan:VariableVolume LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR RETURN FAN Design Size Maximum Flow Rate [m3/s] 0.02400
115 Fan:VariableVolume LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.02400
116 Controller:OutdoorAir LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR OA CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.01250
117 Controller:OutdoorAir LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR OA CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.01250
118 HeatExchanger:AirToAir:SensibleAndLatent LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 0.01250
119 Fan:VariableVolume LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR RETURN FAN Design Size Maximum Flow Rate [m3/s] 0.01250
120 Fan:VariableVolume LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.01250
121 Controller:OutdoorAir LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR OA CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.16000
122 Controller:OutdoorAir LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR OA CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.16000
123 HeatExchanger:AirToAir:SensibleAndLatent LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 0.16000
124 Fan:VariableVolume LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR RETURN FAN Design Size Maximum Flow Rate [m3/s] 0.16000
125 Fan:VariableVolume LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.16000
126 Controller:OutdoorAir LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR OA CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.03069
127 Controller:OutdoorAir LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR OA CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.03069
128 HeatExchanger:AirToAir:SensibleAndLatent LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 0.03069
129 Fan:VariableVolume LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR RETURN FAN Design Size Maximum Flow Rate [m3/s] 0.03069
130 Fan:VariableVolume LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.03069
131 Controller:OutdoorAir LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR OA CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.01263
132 Controller:OutdoorAir LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR OA CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.01263
133 HeatExchanger:AirToAir:SensibleAndLatent LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 0.01263
134 Fan:VariableVolume LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR RETURN FAN Design Size Maximum Flow Rate [m3/s] 0.01263
135 Fan:VariableVolume LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.01263


VRF System Information

VRF System Type VRF System Name VRF System Cooling Combination Ratio VRF System Heating Combination Ratio VRF System Cooling Piping Correction Factor VRF System Heating Piping Correction Factor
1 AirConditioner:VariableRefrigerantFlow LOOP_VRF1_SYSTEM1_UNIDAD_EXTERIOR_DE_BOMBA_DE_CALOR_VRF 1.00000 1.00000 0.94336 1.00000


Zone Surfaces

Zone Name # Surfaces
1 Z01_RECEPCION_CAFETERIA 19
2 Z02_OFICINA 16
3 Z03_SALAS_DEPORTIVAS 18
4 Z04_ZONAS_SECAS_P_1 19
5 Z05_VESTUARIOS_P_1 19
6 Z06_ASEO_1 8
7 Z07_ASEO_2 8
8 Z08_ASEO_ACCESIBLE 9
9 Z09_ASCENSOR 10


Shading Surfaces

Number of Shading Surfaces # Surfaces
1 Number of Shading Surfaces 14


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 Z01_S01_E07 Wall   CTF - ConductionTransferFunction C05_MURO_EXTERIOR 0.354 0.336   2.93 7.13 3.35 180.00 90.00 2.08 3.43 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.70 0.30 4
2 Z01_S01_E07_G1 Window Z01_S01_E07 Window5 Detailed Fenestration H01_WINDOW N/A 0.999 No 3.78 3.78 3.78 180.00 90.00 1.30 2.90 0.36 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.80 0.20 4
3 Z01_S01_E08 Wall   CTF - ConductionTransferFunction C05_MURO_EXTERIOR 0.354 0.336   3.43 3.43 3.43 270.00 90.00 1.00 3.43 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.78 0.22 4
4 Z01_S01_E09 Wall   CTF - ConductionTransferFunction C05_MURO_EXTERIOR 0.354 0.336   3.63 19.38 5.20 180.00 90.00 5.65 3.43 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.58 0.42 4
5 Z01_S01_E09_G1 Window Z01_S01_E09 Window5 Detailed Fenestration H02_WINDOW N/A 0.999 No 8.07 8.07 8.07 180.00 90.00 2.83 2.85 0.36 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.78 0.22 4
6 Z01_S01_E09_G2 Window Z01_S01_E09 Window5 Detailed Fenestration H03_WINDOW N/A 0.999 No 6.11 6.11 6.11 180.00 90.00 2.13 2.87 0.36 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.80 0.20 4
7 Z01_S01_E10 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   6.75 6.75 6.75 270.00 90.00 1.97 3.43 0.00 iz-Z01_S01_E10 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
8 Z01_S01_E11 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   5.93 5.93 5.93 270.00 90.00 1.73 3.43 0.00 iz-Z01_S01_E11 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
9 Z01_S01_E12 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   5.54 5.54 5.54 270.00 90.00 1.62 3.43 0.00 iz-Z01_S01_E12 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
10 Z01_S01_E13 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   26.51 26.51 26.51 0.00 90.00 7.73 3.43 0.00 iz-Z01_S01_E13 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
11 Z01_S01_E14 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   22.23 22.23 22.23 90.00 90.00 6.48 3.43 0.00 iz-Z01_S01_E14 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
12 Z01_S01_E07_G1_TB2_LATERALES V Wall   CTF - ConductionTransferFunction C13_TBW_6_62524U_ 0.151 0.148   7.39 7.39 7.39 180.00 90.00 0.30 24.65 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
13 Z01_S01_TB09 FF Wall   CTF - ConductionTransferFunction C11_TBW_3_18333U_ 0.314 0.300   1.64 1.64 1.64 180.00 90.00 0.30 5.46 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
14 Z01_S01_TB45 P Wall   CTF - ConductionTransferFunction C09_TBW_164_545U_ 6.077E-003 6.072E-003   2.06 2.06 2.06 180.00 90.00 0.30 6.86 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
15 Z01_S01_E01 Floor   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR (INV) 0.383 0.351   30.84 30.84 30.84 90.00 180.00 5.55 5.55 0.00 iz-Z01_S01_E01 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.00 1.00 0.00 10
16 Z01_S01_E03 Floor   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR (INV) 0.383 0.351   10.97 10.97 10.97 90.00 180.00 1.42 7.73 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 1.00 0.00 1.00 0.00 4
17 Z01_S01_E05 Floor   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR (INV) 0.383 0.351   3.53 3.53 3.53 90.00 180.00 1.62 2.18 0.00 iz-Z01_S01_E05 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.00 1.00 0.00 4
18 Z01_S01_E06 Roof   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR 0.383 0.358   48.00 48.00 48.00 270.00 0.00 6.93 6.93 0.00 Z01_S01_E06 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 6
19 Z01_RECEPCION_CAFETERIA FURNITURE Internal Mass   CTF - ConductionTransferFunction FURNIT_INTERNALMASS 3.600 3.600   24.00 24.00 24.00 0.00 90.00 24.00 1.00 0.00 Z01_RECEPCION_CAFETERIA FURNITURE Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 1.00 0.00 0
20 Z02_S01_E04 Wall   CTF - ConductionTransferFunction C03_MEDIANERA 0.274 0.264   1.87 1.87 1.87 270.00 90.00 0.54 3.43 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 1.00 0.50 0.50 0.50 4
21 Z02_S01_E05 Wall   CTF - ConductionTransferFunction C05_MURO_EXTERIOR 0.354 0.336   8.31 8.31 8.31 270.00 90.00 2.42 3.43 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
22 Z02_S01_E06 Wall   CTF - ConductionTransferFunction C05_MURO_EXTERIOR 0.354 0.336   0.86 6.82 1.46 180.00 90.00 1.99 3.43 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.54 0.46 4
23 Z02_S01_E06_G1 Window Z02_S01_E06 Window5 Detailed Fenestration H04_WINDOW N/A 0.999 No 5.36 5.36 5.36 180.00 90.00 1.86 2.88 0.36 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.76 0.24 4
24 Z02_S01_E07 Wall   CTF - ConductionTransferFunction C05_MURO_EXTERIOR 0.354 0.336   0.27 2.12 0.45 90.00 90.00 0.62 3.43 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.92 7.94E-002 4
25 Z02_S01_E07_G1 Window Z02_S01_E07 Window5 Detailed Fenestration H05_WINDOW N/A 0.999 No 1.67 1.67 1.67 90.00 90.00 0.57 2.95 0.36 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.95 4.84E-002 4
26 Z02_S01_E09 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   6.82 6.82 6.82 0.00 90.00 1.99 3.43 0.00 iz-Z02_S01_E09 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
27 Z02_S01_E06_G1_TB2_LATERALES V Wall   CTF - ConductionTransferFunction C15_TBW_8_17309U_ 0.122 0.120   4.38 4.38 4.38 180.00 90.00 0.30 14.60 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
28 Z02_S01_TB06 FC Wall   CTF - ConductionTransferFunction C08_TBW_0_7875U_ 1.270 1.067   0.70 0.70 0.70 180.00 90.00 0.30 2.34 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
29 Z02_S01_TB10 FF Wall   CTF - ConductionTransferFunction C11_TBW_3_18333U_ 0.314 0.300   0.60 0.60 0.60 180.00 90.00 0.30 1.99 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
30 Z02_S01_TB23 P Wall   CTF - ConductionTransferFunction C09_TBW_164_545U_ 6.077E-003 6.072E-003   1.03 1.03 1.03 180.00 90.00 0.30 3.43 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
31 iz-Z01_S01_E10 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   6.75 6.75 6.75 90.00 90.00 1.97 3.43 0.00 Z01_S01_E10 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
32 Z02_S01_E01 Floor   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR (INV) 0.383 0.351   3.22 3.22 3.22 90.00 180.00 1.62 1.99 0.00 iz-Z02_S01_E01 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.00 1.00 0.00 4
33 Z02_S01_E02 Floor   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR (INV) 0.383 0.351   2.52 2.52 2.52 90.00 180.00 1.27 1.99 0.00 iz-Z02_S01_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.00 1.00 0.00 4
34 Z02_S01_E03 Roof   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR 0.383 0.358   5.90 5.90 5.90 180.00 0.00 1.99 2.97 0.00 Z02_S01_E03 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 4
35 Z02_OFICINA FURNITURE Internal Mass   CTF - ConductionTransferFunction FURNIT_INTERNALMASS 3.600 3.600   2.95 2.95 2.95 0.00 90.00 2.95 1.00 0.00 Z02_OFICINA FURNITURE Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 1.00 0.00 0
36 Z03_S01_E04 Wall   CTF - ConductionTransferFunction C05_MURO_EXTERIOR 0.354 0.336   42.22 51.32 43.59 0.00 90.00 14.96 3.43 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 Z03_S01_E04_G1 Window Z03_S01_E04 Window5 Detailed Fenestration H06_WINDOW N/A 0.999 No 3.82 3.82 3.82 0.00 90.00 4.37 0.87 0.36 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.68 0.32 4
38 Z03_S02_E03_G1 Window Z03_S01_E04 Window5 Detailed Fenestration H08_WINDOW N/A 0.999 No 3.91 3.91 3.91 0.00 90.00 4.47 0.87 0.36 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.68 0.32 4
39 Z03_S01_E05 Wall   CTF - ConductionTransferFunction C03_MEDIANERA 0.274 0.264   33.29 33.29 33.29 90.00 90.00 9.71 3.43 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 1.00 0.50 0.50 0.50 4
40 Z03_S01_E06 Wall   CTF - ConductionTransferFunction C05_MURO_EXTERIOR 0.354 0.336   4.28 24.52 6.30 180.00 90.00 7.15 3.43 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.57 0.43 4
41 Z03_S01_E06_G1 Window Z03_S01_E06 Window5 Detailed Fenestration H07_WINDOW N/A 0.999 No 12.14 12.14 12.14 180.00 90.00 4.31 2.82 0.36 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.79 0.21 4
42 Z03_S01_E06_G2 Window Z03_S01_E06 Window5 Detailed Fenestration H03_WINDOW N/A 0.999 No 6.08 6.08 6.08 180.00 90.00 2.12 2.87 0.36 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.80 0.20 4
43 Z03_S02_E04 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   10.77 10.77 10.77 270.00 90.00 3.14 3.43 0.00 iz-Z03_S02_E04 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
44 Z03_S01_E04_G1_TB2_LATERALES V Wall   CTF - ConductionTransferFunction C12_TBW_4_48101U_ 0.223 0.216   9.55 9.55 9.55 180.00 90.00 0.30 31.84 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
45 Z03_S01_TB09 FF Wall   CTF - ConductionTransferFunction C11_TBW_3_18333U_ 0.314 0.300   0.71 0.71 0.71 180.00 90.00 0.30 2.38 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
46 Z03_S01_TB23 P Wall   CTF - ConductionTransferFunction C09_TBW_164_545U_ 6.077E-003 6.072E-003   5.14 5.14 5.14 180.00 90.00 0.30 17.15 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
47 iz-Z01_S01_E13 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   26.51 26.51 26.51 180.00 90.00 7.73 3.43 0.00 Z01_S01_E13 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
48 iz-Z01_S01_E14 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   22.23 22.23 22.23 270.00 90.00 6.48 3.43 0.00 Z01_S01_E14 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
49 Z03_S01_E01 Floor   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR (INV) 0.383 0.351   11.37 11.37 11.37 90.00 180.00 4.78 2.38 0.00 iz-Z03_S01_E01 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.00 1.00 0.00 4
50 Z03_S01_E02 Floor   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR (INV) 0.383 0.351   80.47 80.47 80.47 90.00 180.00 8.97 8.97 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 1.00 0.00 1.00 0.00 8
51 Z03_S01_E03 Roof   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR 0.383 0.358   93.92 93.92 93.92 270.00 0.00 9.69 9.69 0.00 Z03_S01_E03 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 6
52 Z03_SALAS_DEPORTIVAS FURNITURE Internal Mass   CTF - ConductionTransferFunction FURNIT_INTERNALMASS 3.600 3.600   46.83 46.83 46.83 0.00 90.00 46.83 1.00 0.00 Z03_SALAS_DEPORTIVAS FURNITURE Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 1.00 0.00 0
53 Z03_S01_E08 FURNITURE Internal Mass   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.850   21.55 21.55 21.55 0.00 90.00 21.55 1.00 0.00 Z03_S01_E08 FURNITURE Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 1.00 0.00 0
54 Z04_S01_E04 Wall   CTF - ConductionTransferFunction C04_MURO_CON_TERRENO 0.311 0.297   16.14 16.14 16.14 180.00 90.00 4.02 4.02 0.00 Ground N/A-Ground User Supplied Value NoSun NoWind 1.00 0.50 0.50 0.50 6
55 Z04_S01_E06 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   4.90 4.90 4.90 270.00 90.00 1.62 3.03 0.00 iz-Z04_S01_E06 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
56 Z04_S02_E04 Wall   CTF - ConductionTransferFunction C03_MEDIANERA 0.274 0.264   23.60 23.60 23.60 0.00 90.00 7.79 3.03 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 1.00 0.50 0.50 0.50 4
57 Z04_S02_E05 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   3.78 3.78 3.78 270.00 90.00 1.94 1.94 0.00 iz-Z04_S02_E05 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 6
58 Z04_S02_E06 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   9.33 9.33 9.33 90.00 90.00 3.08 3.03 0.00 iz-Z04_S02_E06 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
59 Z04_S02_E07 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   6.77 6.77 6.77 180.00 90.00 2.23 3.03 0.00 iz-Z04_S02_E07 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
60 Z04_S02_E10 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   6.62 6.62 6.62 180.00 90.00 2.18 3.03 0.00 iz-Z04_S02_E10 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
61 Z04_S02_E11 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   6.30 6.30 6.30 0.00 90.00 2.08 3.03 0.00 iz-Z04_S02_E11 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
62 Z04_S02_E12 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   5.24 5.24 5.24 270.00 90.00 1.73 3.03 0.00 iz-Z04_S02_E12 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
63 Z04_S03_E05 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   4.90 4.90 4.90 90.00 90.00 1.62 3.03 0.00 iz-Z04_S03_E05 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
64 Z04_S01_TB03 FS Wall   CTF - ConductionTransferFunction C10_TBW_1_00385U_ 0.996 0.867   1.58 1.58 1.58 180.00 90.00 0.30 5.28 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
65 Z04_S01_TB04 FF Wall   CTF - ConductionTransferFunction C11_TBW_3_18333U_ 0.314 0.300   0.98 0.98 0.98 180.00 90.00 0.30 3.27 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
66 Z04_S01_TB05 FC Wall   CTF - ConductionTransferFunction C08_TBW_0_7875U_ 1.270 1.067   1.82 1.82 1.82 180.00 90.00 0.30 6.06 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
67 Z04_S01_E01 Floor   CTF - ConductionTransferFunction C06_SOLERA_CON_TERRENO (INV) 0.272 0.255   35.84 35.84 35.84 90.00 180.00 5.99 5.99 0.00 Ground N/A-Ground User Supplied Value NoSun NoWind 1.00 0.00 1.00 0.00 10
68 Z04_S01_E02 Roof   CTF - ConductionTransferFunction C01_CUBIERTA_PLANA 0.258 0.246   0.87 0.87 0.87 180.00 0.00 1.40 0.62 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.00 1.00 0.76 0.24 4
69 iz-Z01_S01_E01 Roof   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR 0.383 0.358   30.84 30.84 30.84 270.00 0.00 5.55 5.55 0.00 Z01_S01_E01 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 10
70 iz-Z02_S01_E02 Roof   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR 0.383 0.358   2.52 2.52 2.52 270.00 0.00 1.27 1.99 0.00 Z02_S01_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 4
71 Z04_ZONAS_SECAS_P_1 FURNITURE Internal Mass   CTF - ConductionTransferFunction FURNIT_INTERNALMASS 3.600 3.600   17.63 17.63 17.63 0.00 90.00 17.63 1.00 0.00 Z04_ZONAS_SECAS_P_1 FURNITURE Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 1.00 0.00 0
72 Z04_S01_E05 FURNITURE Internal Mass   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.850   41.80 41.80 41.80 0.00 90.00 41.80 1.00 0.00 Z04_S01_E05 FURNITURE Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 1.00 0.00 0
73 Z05_S01_E04 Wall   CTF - ConductionTransferFunction C04_MURO_CON_TERRENO 0.311 0.297   7.10 7.10 7.10 180.00 90.00 2.40 2.96 0.00 Ground N/A-Ground User Supplied Value NoSun NoWind 1.00 0.50 0.50 0.50 4
74 Z05_S01_E05 Wall   CTF - ConductionTransferFunction C03_MEDIANERA 0.274 0.264   14.30 14.30 14.30 270.00 90.00 3.78 3.78 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 1.00 0.50 0.50 0.50 6
75 Z05_S01_E06 Wall   CTF - ConductionTransferFunction C03_MEDIANERA 0.274 0.264   7.28 7.28 7.28 0.00 90.00 2.40 3.03 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 1.00 0.50 0.50 0.50 4
76 Z05_S01_E07 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   4.78 4.78 4.78 90.00 90.00 1.62 2.96 0.00 iz-Z05_S01_E07 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
77 Z05_S01_E09 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   5.24 5.24 5.24 90.00 90.00 1.73 3.03 0.00 iz-Z05_S01_E09 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
78 Z05_S02_E03 Wall   CTF - ConductionTransferFunction C04_MURO_CON_TERRENO 0.311 0.297   7.28 7.28 7.28 180.00 90.00 2.40 3.03 0.00 Ground N/A-Ground User Supplied Value NoSun NoWind 1.00 0.50 0.50 0.50 4
79 Z05_S02_E04 Wall   CTF - ConductionTransferFunction C03_MEDIANERA 0.274 0.264   7.28 7.28 7.28 0.00 90.00 2.40 3.03 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 1.00 0.50 0.50 0.50 4
80 Z05_S02_E05 Wall   CTF - ConductionTransferFunction C03_MEDIANERA 0.274 0.264   14.48 14.48 14.48 90.00 90.00 4.78 3.03 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 1.00 0.50 0.50 0.50 4
81 Z05_S02_E06 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   4.90 4.90 4.90 270.00 90.00 1.62 3.03 0.00 iz-Z05_S02_E06 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
82 Z05_S01_TB03 FS Wall   CTF - ConductionTransferFunction C10_TBW_1_00385U_ 0.996 0.867   1.44 1.44 1.44 180.00 90.00 0.30 4.81 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
83 Z05_S02_TB04 FF Wall   CTF - ConductionTransferFunction C11_TBW_3_18333U_ 0.314 0.300   0.71 0.71 0.71 180.00 90.00 0.30 2.38 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
84 iz-Z04_S02_E05 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   3.78 3.78 3.78 270.00 90.00 1.94 1.94 0.00 Z04_S02_E05 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 6
85 iz-Z04_S02_E06 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   9.33 9.33 9.33 270.00 90.00 3.08 3.03 0.00 Z04_S02_E06 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
86 Z05_S01_E01 Floor   CTF - ConductionTransferFunction C06_SOLERA_CON_TERRENO (INV) 0.272 0.255   11.48 11.48 11.48 90.00 180.00 4.78 2.40 0.00 Ground N/A-Ground User Supplied Value NoSun NoWind 1.00 0.00 1.00 0.00 4
87 Z05_S02_E01 Floor   CTF - ConductionTransferFunction C06_SOLERA_CON_TERRENO (INV) 0.272 0.255   11.48 11.48 11.48 90.00 180.00 4.78 2.40 0.00 Ground N/A-Ground User Supplied Value NoSun NoWind 1.00 0.00 1.00 0.00 4
88 Z05_S01_E02 Roof   CTF - ConductionTransferFunction C01_CUBIERTA_PLANA 0.258 0.246   5.53 5.53 5.53 180.00 0.00 2.28 2.42 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.00 1.00 0.28 0.72 4
89 Z05_S01_E03 Roof   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR 0.383 0.358   5.61 5.61 5.61 180.00 0.00 2.38 2.36 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 1.00 1.00 0.00 1.00 4
90 iz-Z03_S01_E01 Roof   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR 0.383 0.358   11.37 11.37 11.37 270.00 0.00 4.78 2.38 0.00 Z03_S01_E01 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 4
91 Z05_VESTUARIOS_P_1 FURNITURE Internal Mass   CTF - ConductionTransferFunction FURNIT_INTERNALMASS 3.600 3.600   11.48 11.48 11.48 0.00 90.00 11.48 1.00 0.00 Z05_VESTUARIOS_P_1 FURNITURE Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 1.00 0.00 0
92 Z06_S01_E03 Wall   CTF - ConductionTransferFunction C04_MURO_CON_TERRENO 0.311 0.297   6.77 6.77 6.77 180.00 90.00 2.23 3.03 0.00 Ground N/A-Ground User Supplied Value NoSun NoWind 1.00 0.50 0.50 0.50 4
93 Z06_S01_TB03 FS Wall   CTF - ConductionTransferFunction C10_TBW_1_00385U_ 0.996 0.867   0.67 0.67 0.67 180.00 90.00 0.30 2.23 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
94 Z06_S01_TB04 FF Wall   CTF - ConductionTransferFunction C11_TBW_3_18333U_ 0.314 0.300   0.60 0.60 0.60 180.00 90.00 0.30 1.99 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
95 iz-Z04_S01_E06 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   4.90 4.90 4.90 90.00 90.00 1.62 3.03 0.00 Z04_S01_E06 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
96 iz-Z04_S02_E07 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   6.77 6.77 6.77 0.00 90.00 2.23 3.03 0.00 Z04_S02_E07 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
97 iz-Z05_S01_E07 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   4.78 4.78 4.78 270.00 90.00 1.62 2.96 0.00 Z05_S01_E07 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
98 Z06_S01_E01 Floor   CTF - ConductionTransferFunction C06_SOLERA_CON_TERRENO (INV) 0.272 0.255   3.62 3.62 3.62 90.00 180.00 1.62 2.23 0.00 Ground N/A-Ground User Supplied Value NoSun NoWind 1.00 0.00 1.00 0.00 4
99 iz-Z02_S01_E01 Roof   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR 0.383 0.358   3.22 3.22 3.22 270.00 0.00 1.62 1.99 0.00 Z02_S01_E01 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 4
100 Z07_S01_E03 Wall   CTF - ConductionTransferFunction C04_MURO_CON_TERRENO 0.311 0.297   6.62 6.62 6.62 180.00 90.00 2.18 3.03 0.00 Ground N/A-Ground User Supplied Value NoSun NoWind 1.00 0.50 0.50 0.50 4
101 Z07_S01_TB03 FS Wall   CTF - ConductionTransferFunction C10_TBW_1_00385U_ 0.996 0.867   0.66 0.66 0.66 180.00 90.00 0.30 2.18 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
102 Z07_S01_TB04 FF Wall   CTF - ConductionTransferFunction C11_TBW_3_18333U_ 0.314 0.300   0.66 0.66 0.66 180.00 90.00 0.30 2.18 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
103 iz-Z04_S02_E10 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   6.62 6.62 6.62 0.00 90.00 2.18 3.03 0.00 Z04_S02_E10 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
104 iz-Z04_S03_E05 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   4.90 4.90 4.90 270.00 90.00 1.62 3.03 0.00 Z04_S03_E05 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
105 iz-Z05_S02_E06 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   4.90 4.90 4.90 90.00 90.00 1.62 3.03 0.00 Z05_S02_E06 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
106 Z07_S01_E01 Floor   CTF - ConductionTransferFunction C06_SOLERA_CON_TERRENO (INV) 0.272 0.255   3.53 3.53 3.53 90.00 180.00 1.62 2.18 0.00 Ground N/A-Ground User Supplied Value NoSun NoWind 1.00 0.00 1.00 0.00 4
107 iz-Z01_S01_E05 Roof   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR 0.383 0.358   3.53 3.53 3.53 270.00 0.00 1.62 2.18 0.00 Z01_S01_E05 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 4
108 Z08_S01_E03 Wall   CTF - ConductionTransferFunction C05_MURO_EXTERIOR 0.354 0.336   6.12 6.82 6.22 0.00 90.00 1.99 3.43 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
109 Z08_S01_E03_G1 Window Z08_S01_E03 Window5 Detailed Fenestration H09_WINDOW N/A 0.999 No 0.60 0.60 0.60 0.00 90.00 0.64 0.94 0.36 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.78 0.22 4
110 Z08_S01_E04 Wall   CTF - ConductionTransferFunction C03_MEDIANERA 0.274 0.264   16.60 16.60 16.60 270.00 90.00 4.84 3.43 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 1.00 0.50 0.50 0.50 4
111 Z08_S01_E07 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   6.82 6.82 6.82 180.00 90.00 1.99 3.43 0.00 iz-Z08_S01_E07 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
112 Z08_S01_E03_G1_TB2_LATERALES V Wall   CTF - ConductionTransferFunction C14_TBW_6_77308U_ 0.148 0.144   0.81 0.81 0.81 180.00 90.00 0.30 2.70 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
113 iz-Z01_S01_E12 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   5.54 5.54 5.54 90.00 90.00 1.62 3.43 0.00 Z01_S01_E12 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
114 iz-Z03_S02_E04 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   10.77 10.77 10.77 90.00 90.00 3.14 3.43 0.00 Z03_S02_E04 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
115 Z08_S01_E01 Floor   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR (INV) 0.383 0.351   9.23 9.23 9.23 90.00 180.00 4.65 1.99 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 1.00 0.00 1.00 0.00 4
116 Z08_S01_E02 Roof   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR 0.383 0.358   9.62 9.62 9.62 180.00 0.00 1.99 4.84 0.00 Z08_S01_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 4
117 Z09_S01_E02 Wall   CTF - ConductionTransferFunction C03_MEDIANERA 0.274 0.264   6.30 6.30 6.30 0.00 90.00 2.08 3.03 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 1.00 0.50 0.50 0.50 4
118 Z09_S02_E02 Wall   CTF - ConductionTransferFunction C03_MEDIANERA 0.274 0.264   5.93 5.93 5.93 270.00 90.00 1.73 3.43 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 1.00 0.50 0.50 0.50 4
119 iz-Z01_S01_E11 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   5.93 5.93 5.93 90.00 90.00 1.73 3.43 0.00 Z01_S01_E11 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
120 iz-Z02_S01_E09 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   6.82 6.82 6.82 180.00 90.00 1.99 3.43 0.00 Z02_S01_E09 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
121 iz-Z04_S02_E11 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   6.30 6.30 6.30 180.00 90.00 2.08 3.03 0.00 Z04_S02_E11 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
122 iz-Z04_S02_E12 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   5.24 5.24 5.24 90.00 90.00 1.73 3.03 0.00 Z04_S02_E12 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
123 iz-Z05_S01_E09 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   5.24 5.24 5.24 270.00 90.00 1.73 3.03 0.00 Z05_S01_E09 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
124 iz-Z08_S01_E07 Wall   CTF - ConductionTransferFunction C07_TABIQUE_INTERIOR 0.850 0.754   6.82 6.82 6.82 0.00 90.00 1.99 3.43 0.00 Z08_S01_E07 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
125 Z09_S01_E01 Floor   CTF - ConductionTransferFunction C06_SOLERA_CON_TERRENO (INV) 0.272 0.255   3.59 3.59 3.59 90.00 180.00 1.73 2.08 0.00 Ground N/A-Ground User Supplied Value NoSun NoWind 1.00 0.00 1.00 0.00 4
126 Z09_S02_E01 Roof   CTF - ConductionTransferFunction C02_FORJADO_INTERIOR 0.383 0.358   3.43 3.43 3.43 180.00 0.00 1.99 1.73 0.00 Z09_S02_E01 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 4


Shading Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Transmittance Schedule Min Schedule Value Max Schedule Value Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 SHDW_B_01 Detached Shading:Building   None   0.0 0.0   1.40 1.40 1.40 90.00 0.00 1.00 1.40                     4
2 Mir-SHDW_B_01 Detached Shading:Building   None   0.0 0.0   1.40 1.40 1.40 270.00 180.00 1.00 1.40                     4
3 SHDW_B_02 Detached Shading:Building   None   0.0 0.0   1.40 1.40 1.40 90.00 0.00 1.00 1.40                     4
4 Mir-SHDW_B_02 Detached Shading:Building   None   0.0 0.0   1.40 1.40 1.40 270.00 180.00 1.00 1.40                     4
5 Z01_S01_E09_G1 OH Shading Z01_S01_E09 None   0.0 0.0   5.67 5.67 5.67 0.00 170.00 2.83 2.00                     4
6 Mir-Z01_S01_E09_G1 OH Shading Z01_S01_E09 None   0.0 0.0   5.67 5.67 5.67 180.00 10.00 2.83 2.00                     4
7 Z01_S01_E09_G2 OH Shading Z01_S01_E09 None   0.0 0.0   4.26 4.26 4.26 0.00 170.00 2.13 2.00                     4
8 Mir-Z01_S01_E09_G2 OH Shading Z01_S01_E09 None   0.0 0.0   4.26 4.26 4.26 180.00 10.00 2.13 2.00                     4
9 Z02_S01_E06_G1 OH Shading Z02_S01_E06 None   0.0 0.0   3.72 3.72 3.72 0.00 170.00 1.86 2.00                     4
10 Mir-Z02_S01_E06_G1 OH Shading Z02_S01_E06 None   0.0 0.0   3.72 3.72 3.72 180.00 10.00 1.86 2.00                     4
11 Z03_S01_E06_G1 OH Shading Z03_S01_E06 None   0.0 0.0   8.62 8.62 8.62 0.00 170.00 4.31 2.00                     4
12 Mir-Z03_S01_E06_G1 OH Shading Z03_S01_E06 None   0.0 0.0   8.62 8.62 8.62 180.00 10.00 4.31 2.00                     4
13 Z03_S01_E06_G2 OH Shading Z03_S01_E06 None   0.0 0.0   4.24 4.24 4.24 0.00 170.00 2.12 2.00                     4
14 Mir-Z03_S01_E06_G2 OH Shading Z03_S01_E06 None   0.0 0.0   4.24 4.24 4.24 180.00 10.00 2.12 2.00                     4


Frame/Divider Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m}
1 R01_PUERTA_DE_ACCESO_140_145 (49MM) Frame Z01_S01_E07_G1 Window5 Detailed Fenestration   N/A N/A   0.42 0.42 * N/A N/A 4.90E-002 N/A  
2 R07_VENTANA_SUR_295_300_ (77MM) Frame Z01_S01_E09_G1 Window5 Detailed Fenestration   N/A N/A   0.90 0.90 * N/A N/A 7.70E-002 N/A  
3 R06_VENTANA_SUR_225_230_ (66MM) Frame Z01_S01_E09_G2 Window5 Detailed Fenestration   N/A N/A   0.68 0.68 * N/A N/A 6.60E-002 N/A  
4 R05_VENTANA_SUR_195_200_ (61MM) Frame Z02_S01_E06_G1 Window5 Detailed Fenestration   N/A N/A   0.59 0.59 * N/A N/A 6.10E-002 N/A  
5 R09_VENTANA_SUR_60_65_ (26MM) Frame Z02_S01_E07_G1 Window5 Detailed Fenestration   N/A N/A   0.19 0.19 * N/A N/A 2.60E-002 N/A  
6 R02_VENTANA_NORTE_450_455_ (63MM) Frame Z03_S01_E04_G1 Window5 Detailed Fenestration   N/A N/A   0.68 0.68 * N/A N/A 6.30E-002 N/A  
7 R03_VENTANA_NORTE_460_465_ (63MM) Frame Z03_S02_E03_G1 Window5 Detailed Fenestration   N/A N/A   0.69 0.69 * N/A N/A 6.30E-002 N/A  
8 R08_VENTANA_SUR_450_455_ (92MM) Frame Z03_S01_E06_G1 Window5 Detailed Fenestration   N/A N/A   1.35 1.35 * N/A N/A 9.20E-002 N/A  
9 R06_VENTANA_SUR_225_230_ (66MM) Frame Z03_S01_E06_G2 Window5 Detailed Fenestration   N/A N/A   0.68 0.68 * N/A N/A 6.60E-002 N/A  
10 R04_VENTANA_NORTE_70_75_ (32MM) Frame Z08_S01_E03_G1 Window5 Detailed Fenestration   N/A N/A   0.10 0.10 * N/A N/A 3.20E-002 N/A  


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2007 12/31/2007 Monday 365 Use RunPeriod Specified Day Yes Yes No Yes Yes Clark and Allen


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes WeatherFile 03/25 10/28


Environment:WarmupDays

NumberofWarmupDays
1 6


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 Z01_RECEPCION_CAFETERIA RunPeriod: RUNPERIOD 1 4.7408377696E-002 6.9991498021E-002 Pass Pass 4.4700348135E-002 0.1197377445 Pass Pass
2 Z02_OFICINA RunPeriod: RUNPERIOD 1 9.0001107471E-002 0.1311470099 Pass Pass 9.7567455434E-002 0.3713094858 Pass Pass
3 Z03_SALAS_DEPORTIVAS RunPeriod: RUNPERIOD 1 6.4672760750E-002 7.5561521446E-002 Pass Pass 2.8393221179E-002 0.1233244551 Pass Pass
4 Z04_ZONAS_SECAS_P_1 RunPeriod: RUNPERIOD 1 1.1592398985E-002 1.2264317922E-002 Pass Pass 4.0831524033E-002 0.1120175076 Pass Pass
5 Z05_VESTUARIOS_P_1 RunPeriod: RUNPERIOD 1 4.2641217331E-002 0.1200997039 Pass Pass 0.5247885097 3.4466233748 Pass Pass
6 Z06_ASEO_1 RunPeriod: RUNPERIOD 1 2.2418561653E-003 1.5607531671E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
7 Z07_ASEO_2 RunPeriod: RUNPERIOD 1 2.2784639218E-003 1.5817975039E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 Z08_ASEO_ACCESIBLE RunPeriod: RUNPERIOD 1 8.1577529842E-003 4.3037739749E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
9 Z09_ASCENSOR RunPeriod: RUNPERIOD 1 8.3399932222E-003 4.5710550608E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Report

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Annual Heat Emissions Summary

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [kWh] -4284.1 985.54 0.00 20950.87 4944.65 22596.92



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7°C, ≤ 32.2°C) [hr] Extreme Caution (> 32.2°C, ≤ 39.4°C) [hr] Danger (> 39.4°C, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
Z01_RECEPCION_CAFETERIA 8326.75 433.25 0.00 0.00 0.00
Z02_OFICINA 7895.50 859.00 5.50 0.00 0.00
Z03_SALAS_DEPORTIVAS 8504.50 255.50 0.00 0.00 0.00
Z04_ZONAS_SECAS_P_1 8760.00 0.00 0.00 0.00 0.00
Z05_VESTUARIOS_P_1 8760.00 0.00 0.00 0.00 0.00
Z06_ASEO_1 8760.00 0.00 0.00 0.00 0.00
Z07_ASEO_2 8760.00 0.00 0.00 0.00 0.00
Z08_ASEO_ACCESIBLE 8552.50 207.50 0.00 0.00 0.00
Z09_ASCENSOR 8760.00 0.00 0.00 0.00 0.00
Min 7895.50 0.00 0.00 0.00 0.00
Max 8760.00 859.00 5.50 0.00 0.00
Average 8564.36 195.03 0.61 0.00 0.00
Sum 77079.25 1755.25 5.50 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7°C, ≤ 32.2°C) [hr] Extreme Caution (> 32.2°C, ≤ 39.4°C) [hr] Danger (> 39.4°C, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
Z01_RECEPCION_CAFETERIA 8256.75 0.00 0.00 0.00 0.00
Z02_OFICINA 2218.50 0.00 0.00 0.00 0.00
Z03_SALAS_DEPORTIVAS 47215.00 0.00 0.00 0.00 0.00
Z04_ZONAS_SECAS_P_1 5635.00 0.00 0.00 0.00 0.00
Z05_VESTUARIOS_P_1 0.00 0.00 0.00 0.00 0.00
Z06_ASEO_1 0.00 0.00 0.00 0.00 0.00
Z07_ASEO_2 0.00 0.00 0.00 0.00 0.00
Z08_ASEO_ACCESIBLE 0.00 0.00 0.00 0.00 0.00
Z09_ASCENSOR 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 47215.00 0.00 0.00 0.00 0.00
Average 7036.14 0.00 0.00 0.00 0.00
Sum 63325.25 0.00 0.00 0.00 0.00


Heat Index OccupiedHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7°C, ≤ 32.2°C) [hr] Extreme Caution (> 32.2°C, ≤ 39.4°C) [hr] Danger (> 39.4°C, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
Z01_RECEPCION_CAFETERIA 3757.00 0.00 0.00 0.00 0.00
Z02_OFICINA 2610.00 0.00 0.00 0.00 0.00
Z03_SALAS_DEPORTIVAS 3757.00 0.00 0.00 0.00 0.00
Z04_ZONAS_SECAS_P_1 3235.00 0.00 0.00 0.00 0.00
Z05_VESTUARIOS_P_1 0.00 0.00 0.00 0.00 0.00
Z06_ASEO_1 0.00 0.00 0.00 0.00 0.00
Z07_ASEO_2 0.00 0.00 0.00 0.00 0.00
Z08_ASEO_ACCESIBLE 0.00 0.00 0.00 0.00 0.00
Z09_ASCENSOR 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 3757.00 0.00 0.00 0.00 0.00
Average 1484.33 0.00 0.00 0.00 0.00
Sum 13359.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
Z01_RECEPCION_CAFETERIA 8080.25 679.75 0.00 0.00 0.00
Z02_OFICINA 7786.75 973.25 0.00 0.00 0.00
Z03_SALAS_DEPORTIVAS 7241.75 1518.25 0.00 0.00 0.00
Z04_ZONAS_SECAS_P_1 8705.25 54.75 0.00 0.00 0.00
Z05_VESTUARIOS_P_1 8760.00 0.00 0.00 0.00 0.00
Z06_ASEO_1 8760.00 0.00 0.00 0.00 0.00
Z07_ASEO_2 8760.00 0.00 0.00 0.00 0.00
Z08_ASEO_ACCESIBLE 8345.25 414.75 0.00 0.00 0.00
Z09_ASCENSOR 8760.00 0.00 0.00 0.00 0.00
Min 7241.75 0.00 0.00 0.00 0.00
Max 8760.00 1518.25 0.00 0.00 0.00
Average 8355.47 404.53 0.00 0.00 0.00
Sum 75199.25 3640.75 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
Z01_RECEPCION_CAFETERIA 8127.00 129.75 0.00 0.00 0.00
Z02_OFICINA 2181.94 36.56 0.00 0.00 0.00
Z03_SALAS_DEPORTIVAS 39067.50 8147.50 0.00 0.00 0.00
Z04_ZONAS_SECAS_P_1 5579.50 55.50 0.00 0.00 0.00
Z05_VESTUARIOS_P_1 0.00 0.00 0.00 0.00 0.00
Z06_ASEO_1 0.00 0.00 0.00 0.00 0.00
Z07_ASEO_2 0.00 0.00 0.00 0.00 0.00
Z08_ASEO_ACCESIBLE 0.00 0.00 0.00 0.00 0.00
Z09_ASCENSOR 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 39067.50 8147.50 0.00 0.00 0.00
Average 6106.22 929.92 0.00 0.00 0.00
Sum 54955.94 8369.31 0.00 0.00 0.00


Humidex OccupiedHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
Z01_RECEPCION_CAFETERIA 3701.50 55.50 0.00 0.00 0.00
Z02_OFICINA 2570.50 39.50 0.00 0.00 0.00
Z03_SALAS_DEPORTIVAS 3240.50 516.50 0.00 0.00 0.00
Z04_ZONAS_SECAS_P_1 3202.75 32.25 0.00 0.00 0.00
Z05_VESTUARIOS_P_1 0.00 0.00 0.00 0.00 0.00
Z06_ASEO_1 0.00 0.00 0.00 0.00 0.00
Z07_ASEO_2 0.00 0.00 0.00 0.00 0.00
Z08_ASEO_ACCESIBLE 0.00 0.00 0.00 0.00 0.00
Z09_ASCENSOR 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 3701.50 516.50 0.00 0.00 0.00
Average 1412.81 71.53 0.00 0.00 0.00
Sum 12715.25 643.75 0.00 0.00 0.00


Hours of Safety for Cold Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
Z01_RECEPCION_CAFETERIA 8760.00 - 0.00 0.00 0.00
Z02_OFICINA 8760.00 - 0.00 0.00 0.00
Z03_SALAS_DEPORTIVAS 8760.00 - 0.00 0.00 0.00
Z04_ZONAS_SECAS_P_1 8760.00 - 0.00 0.00 0.00
Z05_VESTUARIOS_P_1 0.00 - 0.00 0.00 0.00
Z06_ASEO_1 0.00 - 0.00 0.00 0.00
Z07_ASEO_2 0.00 - 0.00 0.00 0.00
Z08_ASEO_ACCESIBLE 0.00 - 0.00 0.00 0.00
Z09_ASCENSOR 0.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 3893.33 - 0.00 0.00 0.00
Sum 35040.00 - 0.00 0.00 0.00


Hours of Safety for Heat Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
Z01_RECEPCION_CAFETERIA 5535.25 19-AUG-15:15 16.50 0.00 0.00
Z02_OFICINA 4166.50 23-JUN-14:30 127.00 0.00 0.00
Z03_SALAS_DEPORTIVAS 8760.00 - 0.00 0.00 0.00
Z04_ZONAS_SECAS_P_1 8760.00 - 0.00 0.00 0.00
Z05_VESTUARIOS_P_1 0.00 - 0.00 0.00 0.00
Z06_ASEO_1 0.00 - 0.00 0.00 0.00
Z07_ASEO_2 0.00 - 0.00 0.00 0.00
Z08_ASEO_ACCESIBLE 0.00 - 0.00 0.00 0.00
Z09_ASCENSOR 0.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 127.00 0.00 0.00
Average 3024.64 - 15.94 0.00 0.00
Sum 27221.75 - 143.50 0.00 0.00


Unmet Degree-Hours

Cooling Setpoint Unmet Degree-Hours [°C·hr] Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°C·hr] Cooling Setpoint Unmet Occupied Degree-Hours [°C·hr] Heating Setpoint Unmet Degree-Hours [°C·hr] Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°C·hr] Heating Setpoint Unmet Occupied Degree-Hours [°C·hr]
Z01_RECEPCION_CAFETERIA 57.47 114.68 57.47 0.03 0.04 0.03
Z02_OFICINA 58.00 51.36 58.00 0.52 0.39 0.52
Z03_SALAS_DEPORTIVAS 1.71 13.32 1.71 0.88 4.88 0.88
Z04_ZONAS_SECAS_P_1 0.00 0.00 0.00 121.98 225.03 121.98
Z05_VESTUARIOS_P_1 0.00 0.00 0.00 2120.74 0.00 0.00
Z06_ASEO_1 0.00 0.00 0.00 0.00 0.00 0.00
Z07_ASEO_2 0.00 0.00 0.00 0.00 0.00 0.00
Z08_ASEO_ACCESIBLE 0.00 0.00 0.00 0.00 0.00 0.00
Z09_ASCENSOR 0.00 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00 0.00
Max 58.00 114.68 58.00 2120.74 225.03 121.98
Average 13.02 19.93 13.02 249.35 25.59 13.71
Sum 117.19 179.36 117.19 2244.15 230.34 123.41


Discomfort-weighted Exceedance OccupantHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
Z01_RECEPCION_CAFETERIA 0.00 0.00 0.00 0.00
Z02_OFICINA 0.00 0.00 0.00 0.00
Z03_SALAS_DEPORTIVAS 0.00 0.00 0.00 0.00
Z04_ZONAS_SECAS_P_1 0.00 0.00 0.00 0.00
Z05_VESTUARIOS_P_1 0.00 0.00 0.00 0.00
Z06_ASEO_1 0.00 0.00 0.00 0.00
Z07_ASEO_2 0.00 0.00 0.00 0.00
Z08_ASEO_ACCESIBLE 0.00 0.00 0.00 0.00
Z09_ASCENSOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00


Discomfort-weighted Exceedance OccupiedHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
Z01_RECEPCION_CAFETERIA 0.00 0.00 0.00 0.00
Z02_OFICINA 0.00 0.00 0.00 0.00
Z03_SALAS_DEPORTIVAS 0.00 0.00 0.00 0.00
Z04_ZONAS_SECAS_P_1 0.00 0.00 0.00 0.00
Z05_VESTUARIOS_P_1 0.00 0.00 0.00 0.00
Z06_ASEO_1 0.00 0.00 0.00 0.00
Z07_ASEO_2 0.00 0.00 0.00 0.00
Z08_ASEO_ACCESIBLE 0.00 0.00 0.00 0.00
Z09_ASCENSOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
None            


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 0.00 0      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
Z01_S01_E07 C05_MURO_EXTERIOR 0.40 0.336 0.354 7.13 2.93 180.00 90.00 S
Z01_S01_E08 C05_MURO_EXTERIOR 0.40 0.336 0.354 3.43 3.43 270.00 90.00 W
Z01_S01_E09 C05_MURO_EXTERIOR 0.40 0.336 0.354 19.38 3.63 180.00 90.00 S
Z01_S01_E07_G1_TB2_LATERALES V C13_TBW_6_62524U_ 0.40 0.148 0.151 7.39 7.39 180.00 90.00 S
Z01_S01_TB09 FF C11_TBW_3_18333U_ 0.40 0.300 0.314 1.64 1.64 180.00 90.00 S
Z01_S01_TB45 P C09_TBW_164_545U_ 0.40 0.006 0.006 2.06 2.06 180.00 90.00 S
Z01_S01_E03 C02_FORJADO_INTERIOR (INV) 0.40 0.357 0.383 10.97 10.97 90.00 180.00  
Z02_S01_E04 C03_MEDIANERA 0.40 0.264 0.274 1.87 1.87 270.00 90.00 W
Z02_S01_E05 C05_MURO_EXTERIOR 0.40 0.336 0.354 8.31 8.31 270.00 90.00 W
Z02_S01_E06 C05_MURO_EXTERIOR 0.40 0.336 0.354 6.82 0.86 180.00 90.00 S
Z02_S01_E07 C05_MURO_EXTERIOR 0.40 0.336 0.354 2.12 0.27 90.00 90.00 E
Z02_S01_E06_G1_TB2_LATERALES V C15_TBW_8_17309U_ 0.40 0.120 0.122 4.38 4.38 180.00 90.00 S
Z02_S01_TB06 FC C08_TBW_0_7875U_ 0.40 1.067 1.270 0.70 0.70 180.00 90.00 S
Z02_S01_TB10 FF C11_TBW_3_18333U_ 0.40 0.300 0.314 0.60 0.60 180.00 90.00 S
Z02_S01_TB23 P C09_TBW_164_545U_ 0.40 0.006 0.006 1.03 1.03 180.00 90.00 S
Z03_S01_E04 C05_MURO_EXTERIOR 0.40 0.336 0.354 51.32 42.22 0.00 90.00 N
Z03_S01_E05 C03_MEDIANERA 0.40 0.264 0.274 33.29 33.29 90.00 90.00 E
Z03_S01_E06 C05_MURO_EXTERIOR 0.40 0.336 0.354 24.52 4.28 180.00 90.00 S
Z03_S01_E04_G1_TB2_LATERALES V C12_TBW_4_48101U_ 0.40 0.216 0.223 9.55 9.55 180.00 90.00 S
Z03_S01_TB09 FF C11_TBW_3_18333U_ 0.40 0.300 0.314 0.71 0.71 180.00 90.00 S
Z03_S01_TB23 P C09_TBW_164_545U_ 0.40 0.006 0.006 5.14 5.14 180.00 90.00 S
Z03_S01_E02 C02_FORJADO_INTERIOR (INV) 0.40 0.357 0.383 80.47 80.47 90.00 180.00  
Z04_S01_E04 C04_MURO_CON_TERRENO 0.40 0.300 0.311 16.14 16.14 180.00 90.00 S
Z04_S02_E04 C03_MEDIANERA 0.40 0.264 0.274 23.60 23.60 0.00 90.00 N
Z04_S01_TB03 FS C10_TBW_1_00385U_ 0.40 0.867 0.996 1.58 1.58 180.00 90.00 S
Z04_S01_TB04 FF C11_TBW_3_18333U_ 0.40 0.300 0.314 0.98 0.98 180.00 90.00 S
Z04_S01_TB05 FC C08_TBW_0_7875U_ 0.40 1.067 1.270 1.82 1.82 180.00 90.00 S
Z04_S01_E01 C06_SOLERA_CON_TERRENO (INV) 0.40 0.260 0.272 35.84 35.84 90.00 180.00  
Z04_S01_E02 C01_CUBIERTA_PLANA 0.40 0.249 0.258 0.87 0.87 180.00 0.00  
Z05_S01_E04 C04_MURO_CON_TERRENO 0.40 0.300 0.311 7.10 7.10 180.00 90.00 S
Z05_S01_E05 C03_MEDIANERA 0.40 0.264 0.274 14.30 14.30 270.00 90.00 W
Z05_S01_E06 C03_MEDIANERA 0.40 0.264 0.274 7.28 7.28 0.00 90.00 N
Z05_S02_E03 C04_MURO_CON_TERRENO 0.40 0.300 0.311 7.28 7.28 180.00 90.00 S
Z05_S02_E04 C03_MEDIANERA 0.40 0.264 0.274 7.28 7.28 0.00 90.00 N
Z05_S02_E05 C03_MEDIANERA 0.40 0.264 0.274 14.48 14.48 90.00 90.00 E
Z05_S01_TB03 FS C10_TBW_1_00385U_ 0.40 0.867 0.996 1.44 1.44 180.00 90.00 S
Z05_S02_TB04 FF C11_TBW_3_18333U_ 0.40 0.300 0.314 0.71 0.71 180.00 90.00 S
Z05_S01_E01 C06_SOLERA_CON_TERRENO (INV) 0.40 0.260 0.272 11.48 11.48 90.00 180.00  
Z05_S02_E01 C06_SOLERA_CON_TERRENO (INV) 0.40 0.260 0.272 11.48 11.48 90.00 180.00  
Z05_S01_E02 C01_CUBIERTA_PLANA 0.40 0.249 0.258 5.53 5.53 180.00 0.00  
Z05_S01_E03 C02_FORJADO_INTERIOR 0.40 0.364 0.383 5.61 5.61 180.00 0.00  
Z06_S01_E03 C04_MURO_CON_TERRENO 0.40 0.300 0.311 6.77 6.77 180.00 90.00 S
Z06_S01_TB03 FS C10_TBW_1_00385U_ 0.40 0.867 0.996 0.67 0.67 180.00 90.00 S
Z06_S01_TB04 FF C11_TBW_3_18333U_ 0.40 0.300 0.314 0.60 0.60 180.00 90.00 S
Z06_S01_E01 C06_SOLERA_CON_TERRENO (INV) 0.40 0.260 0.272 3.62 3.62 90.00 180.00  
Z07_S01_E03 C04_MURO_CON_TERRENO 0.40 0.300 0.311 6.62 6.62 180.00 90.00 S
Z07_S01_TB03 FS C10_TBW_1_00385U_ 0.40 0.867 0.996 0.66 0.66 180.00 90.00 S
Z07_S01_TB04 FF C11_TBW_3_18333U_ 0.40 0.300 0.314 0.66 0.66 180.00 90.00 S
Z07_S01_E01 C06_SOLERA_CON_TERRENO (INV) 0.40 0.260 0.272 3.53 3.53 90.00 180.00  
Z08_S01_E03 C05_MURO_EXTERIOR 0.40 0.336 0.354 6.82 6.12 0.00 90.00 N
Z08_S01_E04 C03_MEDIANERA 0.40 0.264 0.274 16.60 16.60 270.00 90.00 W
Z08_S01_E03_G1_TB2_LATERALES V C14_TBW_6_77308U_ 0.40 0.144 0.148 0.81 0.81 180.00 90.00 S
Z08_S01_E01 C02_FORJADO_INTERIOR (INV) 0.40 0.357 0.383 9.23 9.23 90.00 180.00  
Z09_S01_E02 C03_MEDIANERA 0.40 0.264 0.274 6.30 6.30 0.00 90.00 N
Z09_S02_E02 C03_MEDIANERA 0.40 0.264 0.274 5.93 5.93 270.00 90.00 W
Z09_S01_E01 C06_SOLERA_CON_TERRENO (INV) 0.40 0.260 0.272 3.59 3.59 90.00 180.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
Z01_S01_E10 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 6.75 6.75 270.00 90.00 W
Z01_S01_E11 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 5.93 5.93 270.00 90.00 W
Z01_S01_E12 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 5.54 5.54 270.00 90.00 W
Z01_S01_E13 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 26.51 26.51 0.00 90.00 N
Z01_S01_E14 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 22.23 22.23 90.00 90.00 E
Z01_S01_E01 C02_FORJADO_INTERIOR (INV) 0.40 0.348 0.383 30.84 30.84 90.00 180.00  
Z01_S01_E05 C02_FORJADO_INTERIOR (INV) 0.40 0.348 0.383 3.53 3.53 90.00 180.00  
Z01_S01_E06 C02_FORJADO_INTERIOR 0.40 0.354 0.383 48.00 48.00 270.00 0.00  
Z02_S01_E09 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 6.82 6.82 0.00 90.00 N
iz-Z01_S01_E10 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 6.75 6.75 90.00 90.00 E
Z02_S01_E01 C02_FORJADO_INTERIOR (INV) 0.40 0.348 0.383 3.22 3.22 90.00 180.00  
Z02_S01_E02 C02_FORJADO_INTERIOR (INV) 0.40 0.348 0.383 2.52 2.52 90.00 180.00  
Z02_S01_E03 C02_FORJADO_INTERIOR 0.40 0.354 0.383 5.90 5.90 180.00 0.00  
Z03_S02_E04 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 10.77 10.77 270.00 90.00 W
iz-Z01_S01_E13 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 26.51 26.51 180.00 90.00 S
iz-Z01_S01_E14 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 22.23 22.23 270.00 90.00 W
Z03_S01_E01 C02_FORJADO_INTERIOR (INV) 0.40 0.348 0.383 11.37 11.37 90.00 180.00  
Z03_S01_E03 C02_FORJADO_INTERIOR 0.40 0.354 0.383 93.92 93.92 270.00 0.00  
Z04_S01_E06 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 4.90 4.90 270.00 90.00 W
Z04_S02_E05 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 3.78 3.78 270.00 90.00 W
Z04_S02_E06 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 9.33 9.33 90.00 90.00 E
Z04_S02_E07 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 6.77 6.77 180.00 90.00 S
Z04_S02_E10 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 6.62 6.62 180.00 90.00 S
Z04_S02_E11 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 6.30 6.30 0.00 90.00 N
Z04_S02_E12 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 5.24 5.24 270.00 90.00 W
Z04_S03_E05 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 4.90 4.90 90.00 90.00 E
iz-Z01_S01_E01 C02_FORJADO_INTERIOR 0.40 0.348 0.383 30.84 30.84 270.00 0.00  
iz-Z02_S01_E02 C02_FORJADO_INTERIOR 0.40 0.348 0.383 2.52 2.52 270.00 0.00  
Z05_S01_E07 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 4.78 4.78 90.00 90.00 E
Z05_S01_E09 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 5.24 5.24 90.00 90.00 E
Z05_S02_E06 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 4.90 4.90 270.00 90.00 W
iz-Z04_S02_E05 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 3.78 3.78 270.00 90.00 W
iz-Z04_S02_E06 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 9.33 9.33 270.00 90.00 W
iz-Z03_S01_E01 C02_FORJADO_INTERIOR 0.40 0.348 0.383 11.37 11.37 270.00 0.00  
iz-Z04_S01_E06 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 4.90 4.90 90.00 90.00 E
iz-Z04_S02_E07 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 6.77 6.77 0.00 90.00 N
iz-Z05_S01_E07 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 4.78 4.78 270.00 90.00 W
iz-Z02_S01_E01 C02_FORJADO_INTERIOR 0.40 0.348 0.383 3.22 3.22 270.00 0.00  
iz-Z04_S02_E10 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 6.62 6.62 0.00 90.00 N
iz-Z04_S03_E05 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 4.90 4.90 270.00 90.00 W
iz-Z05_S02_E06 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 4.90 4.90 90.00 90.00 E
iz-Z01_S01_E05 C02_FORJADO_INTERIOR 0.40 0.348 0.383 3.53 3.53 270.00 0.00  
Z08_S01_E07 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 6.82 6.82 180.00 90.00 S
iz-Z01_S01_E12 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 5.54 5.54 90.00 90.00 E
iz-Z03_S02_E04 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 10.77 10.77 90.00 90.00 E
Z08_S01_E02 C02_FORJADO_INTERIOR 0.40 0.354 0.383 9.62 9.62 180.00 0.00  
iz-Z01_S01_E11 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 5.93 5.93 90.00 90.00 E
iz-Z02_S01_E09 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 6.82 6.82 180.00 90.00 S
iz-Z04_S02_E11 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 6.30 6.30 180.00 90.00 S
iz-Z04_S02_E12 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 5.24 5.24 90.00 90.00 E
iz-Z05_S01_E09 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 5.24 5.24 270.00 90.00 W
iz-Z08_S01_E07 C07_TABIQUE_INTERIOR 0.40 0.706 0.850 6.82 6.82 0.00 90.00 N
Z09_S02_E01 C02_FORJADO_INTERIOR 0.40 0.354 0.383 3.43 3.43 180.00 0.00  
Z01_RECEPCION_CAFETERIA FURNITURE FURNIT_INTERNALMASS 0.40   3.600 24.00   0.00 90.00 N
Z02_OFICINA FURNITURE FURNIT_INTERNALMASS 0.40   3.600 2.95   0.00 90.00 N
Z03_SALAS_DEPORTIVAS FURNITURE FURNIT_INTERNALMASS 0.40   3.600 46.83   0.00 90.00 N
Z03_S01_E08 FURNITURE C07_TABIQUE_INTERIOR 0.40   0.850 21.55   0.00 90.00 N
Z04_ZONAS_SECAS_P_1 FURNITURE FURNIT_INTERNALMASS 0.40   3.600 17.63   0.00 90.00 N
Z04_S01_E05 FURNITURE C07_TABIQUE_INTERIOR 0.40   0.850 41.80   0.00 90.00 N
Z05_VESTUARIOS_P_1 FURNITURE FURNIT_INTERNALMASS 0.40   3.600 11.48   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
Z01_S01_E07_G1 H01_WINDOW R01_PUERTA_DE_ACCESO_140_145 (49MM) 3.78 0.42 0.00 4.20 4.20 0.999 0.581 0.505 8.765 0.000 CurtainWall 1.283 0.538 0.456 No Z01_S01_E07 180.00 90.00 S
Z01_S01_E09_G1 H02_WINDOW R07_VENTANA_SUR_295_300_ (77MM) 8.07 0.90 0.00 8.96 8.96 0.999 0.401 0.315 2.293 0.000 CurtainWall 1.128 0.356 0.268 No Z01_S01_E09 180.00 90.00 S
Z01_S01_E09_G2 H03_WINDOW R06_VENTANA_SUR_225_230_ (66MM) 6.11 0.68 0.00 6.79 6.79 0.999 0.401 0.315 2.293 0.000 CurtainWall 1.115 0.362 0.275 No Z01_S01_E09 180.00 90.00 S
Z02_S01_E06_G1 H04_WINDOW R05_VENTANA_SUR_195_200_ (61MM) 5.36 0.59 0.00 5.95 5.95 0.999 0.401 0.315 2.293 0.000 CurtainWall 1.108 0.366 0.278 No Z02_S01_E06 180.00 90.00 S
Z02_S01_E07_G1 H05_WINDOW R09_VENTANA_SUR_60_65_ (26MM) 1.67 0.19 0.00 1.86 1.86 0.999 0.401 0.315 2.293 0.000 CurtainWall 1.064 0.389 0.299 No Z02_S01_E07 90.00 90.00 E
Z03_S01_E04_G1 H06_WINDOW R02_VENTANA_NORTE_450_455_ (63MM) 3.82 0.68 0.00 4.50 4.50 0.999 0.581 0.505 2.293 0.000 CurtainWall 0.945 0.507 0.443 Yes Z03_S01_E04 0.00 90.00 N
Z03_S02_E03_G1 H08_WINDOW R03_VENTANA_NORTE_460_465_ (63MM) 3.91 0.69 0.00 4.60 4.60 0.999 0.581 0.505 2.293 0.000 CurtainWall 1.111 0.518 0.443 No Z03_S01_E04 0.00 90.00 N
Z03_S01_E06_G1 H07_WINDOW R08_VENTANA_SUR_450_455_ (92MM) 12.14 1.35 0.00 13.49 13.49 0.999 0.341 0.253 2.293 0.000 CurtainWall 1.147 0.301 0.208 No Z03_S01_E06 180.00 90.00 S
Z03_S01_E06_G2 H03_WINDOW R06_VENTANA_SUR_225_230_ (66MM) 6.08 0.68 0.00 6.76 6.76 0.999 0.401 0.315 2.293 0.000 CurtainWall 1.115 0.362 0.275 No Z03_S01_E06 180.00 90.00 S
Z08_S01_E03_G1 H09_WINDOW R04_VENTANA_NORTE_70_75_ (32MM) 0.60 0.10 0.00 0.70 0.70 0.999 0.581 0.505 2.293 0.000 CurtainWall 1.071 0.549 0.473 No Z08_S01_E03 0.00 90.00 N
Total or Average             57.80 0.999 0.430 0.346                      
North Total or Average             9.80 0.999 0.581 0.505                      
Non-North Total or Average             48.01 0.999 0.399 0.314                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
H06_WINDOW:WSC_MAT_1_ESTORES_INTERIORES:INT R02_VENTANA_NORTE_450_455_ (63MM) 0.811 0.571 0.308 CurtainWall 0.945 0.065 0.270


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
Z01_S01_E07_G1 0.00 0.38 0.33 0.00 0.00 0.00 0.00 0.72 0.54
Z01_S01_E09_G1 0.19 0.17 0.23 0.00 0.05 0.06 0.68 0.53 0.57
Z01_S01_E09_G2 0.15 0.13 0.22 0.00 0.05 0.08 0.62 0.51 0.56
Z02_S01_E06_G1 0.22 0.30 0.32 0.00 0.08 0.10 0.68 0.55 0.59
Z02_S01_E07_G1 0.30 0.00 0.00 0.00 0.07 0.00 0.49 0.00 0.00
Z03_S01_E04_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z03_S02_E03_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z03_S01_E06_G1 0.53 0.15 0.13 0.00 0.03 0.04 0.76 0.51 0.54
Z03_S01_E06_G2 0.16 0.22 0.13 0.00 0.07 0.05 0.63 0.54 0.52
Z08_S01_E03_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
Z03_S01_E04_G1 WSC_CTRL_3_1_ESTORES_INTERIORES Interior Shade H06_WINDOW:WSC_MAT_1_ESTORES_INTERIORES:INT Uncontrolled No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
Z01_RECEPCION_CAFETERIA_IG2 LIGHTS Z01_RECEPCION_CAFETERIA Z01_RECEPCION_CAFETERIA GENERAL 3.2498 48.00 156.00 1 SCHED5 42.28 89.02 42.28 0.0000 Y 343.90
Z02_OFICINA_IG2 LIGHTS Z02_OFICINA Z02_OFICINA GENERAL 4.4078 5.90 26.00 1 SCHED12 50.05 50.05 50.05 0.0000 Y 67.86
Z03_SALAS_DEPORTIVAS_IG2 LIGHTS Z03_SALAS_DEPORTIVAS Z03_SALAS_DEPORTIVAS GENERAL 2.7760 93.66 260.00 1 SCHED15 48.03 89.02 48.03 0.0000 Y 651.12
Z03_SALAS_DEPORTIVAS_IG3 LIGHTS Z03_SALAS_DEPORTIVAS Z03_SALAS_DEPORTIVAS GENERAL 1.3880 93.66 130.00 1 SCHED15 48.03 89.02 48.03 0.0000 Y 325.56
Z04_ZONAS_SECAS_P_1_IG2 LIGHTS Z04_ZONAS_SECAS_P_1 Z04_ZONAS_SECAS_P_1 GENERAL 0.3687 35.26 13.00 1 SCHED19 54.03 62.04 54.03 0.0000 Y 36.63
Z04_ZONAS_SECAS_P_1_IG3 LIGHTS Z04_ZONAS_SECAS_P_1 Z04_ZONAS_SECAS_P_1 GENERAL 1.4748 35.26 52.00 1 SCHED20 34.77 72.05 34.77 0.0000 Y 94.29
Z04_ZONAS_SECAS_P_1_IG4 LIGHTS Z04_ZONAS_SECAS_P_1 Z04_ZONAS_SECAS_P_1 GENERAL 0.3687 35.26 13.00 1 SCHED19 54.03 62.04 54.03 0.0000 Y 36.63
Z05_VESTUARIOS_P_1_IG1 LIGHTS Z05_VESTUARIOS_P_1 Z05_VESTUARIOS_P_1 GENERAL 0.8490 22.97 19.50 1 SCHED7 72.05 72.05 72.05 0.0000 Y 73.26
Z06_ASEO_1_IG1 LIGHTS Z06_ASEO_1 Z06_ASEO_1 GENERAL 1.2448 3.62 4.50 1 SCHED21 18.01 72.05 18.01 0.0000 Y 4.23
Z07_ASEO_2_IG1 LIGHTS Z07_ASEO_2 Z07_ASEO_2 GENERAL 1.2735 3.53 4.50 1 SCHED21 18.01 72.05 18.01 0.0000 Y 4.23
Z08_ASEO_ACCESIBLE_IG1 LIGHTS Z08_ASEO_ACCESIBLE Z08_ASEO_ACCESIBLE GENERAL 1.2992 9.62 12.50 1 SCHED21 18.01 72.05 18.01 0.0000 Y 11.74
Interior Lighting Total       1.7868 386.73 691.00               1649.44


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
Exterior Lighting Total 0.00           0.00



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
None                  


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coils [ SEER2 ]

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP2 [W/W] EER2 [Btu/W-h] SEER2 User [Btu/W-h] SEER2 Standard [Btu/W-h] IEER2 [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


Water-to-Air Heat Pumps at Rated Temperatures Report

Coil Type Rated Total Capacity [W] Rated Sensible Capacity [W] Rated Power[W] Rated COP [W/W] Rated Air Dry-bulb Temperature [C] Rated Air Wet-bulb Temperature [C] Rated Water Temperature [C] Design Day used for Sizing
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


DX Heating Coils [ HSPF2 ]

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF2 [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
None        


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS SUPPLY FAN Fan:OnOff 0.70 140.00 0.10 20.47 200.00 1.00 7.69 General    
UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS SUPPLY FAN Fan:OnOff 0.70 140.00 0.03 5.45 200.00 1.00 21.85 General    
UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS SUPPLY FAN Fan:OnOff 0.70 140.00 0.19 37.28 200.00 1.00 5.35 General    
UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS SUPPLY FAN Fan:OnOff 0.70 140.00 0.03 6.14 200.00 1.00 19.69 General    
UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS SUPPLY FAN Fan:OnOff 0.70 140.00 0.02 3.71 200.00 1.00 30.90 General    
LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR RETURN FAN Fan:VariableVolume 0.70 0.00 0.02 0.00 0.00 1.00 0.00 General    
LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR SUPPLY FAN Fan:VariableVolume 0.70 0.00 0.02 0.00 0.00 1.00 0.00 General    
LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR RETURN FAN Fan:VariableVolume 0.70 0.00 0.01 0.00 0.00 1.00 0.00 General    
LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR SUPPLY FAN Fan:VariableVolume 0.70 0.00 0.01 0.00 0.00 1.00 0.00 General    
LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR RETURN FAN Fan:VariableVolume 0.70 0.00 0.16 0.00 0.00 1.00 0.00 General    
LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR SUPPLY FAN Fan:VariableVolume 0.70 0.00 0.16 0.00 0.00 1.00 0.00 General    
LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR RETURN FAN Fan:VariableVolume 0.70 0.00 0.03 0.00 0.00 1.00 0.00 General    
LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR SUPPLY FAN Fan:VariableVolume 0.70 0.00 0.03 0.00 0.00 1.00 0.00 General    
LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR RETURN FAN Fan:VariableVolume 0.70 0.00 0.01 0.00 0.00 1.00 0.00 General    
LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR SUPPLY FAN Fan:VariableVolume 0.70 0.00 0.01 0.00 0.00 1.00 0.00 General    


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
None                


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
None            



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
Z01_RECEPCION_CAFETERIA 1415.94 1415.94 29.50 0.102 0.102 WINTER 1/13 15:00:00 25.00 25.00 0.00808 11.40 0.00500 0.024 0.00
Z02_OFICINA 377.10 377.10 63.93 0.027 0.027 SUMMER 7/22 14:00:00 25.00 25.00 0.00824 34.30 0.00979 0.013 0.00
Z03_SALAS_DEPORTIVAS 2577.90 2577.90 27.52 0.186 0.186 SUMMER 7/22 20:00:00 25.00 24.99 0.01082 31.60 0.01075 0.160 0.00
Z04_ZONAS_SECAS_P_1 3.96 3.96 0.11 0.000 0.031 SUMMER 7/23 19:00:00 25.00 25.00 0.01042 30.90 0.01061 0.031 0.00
Z05_VESTUARIOS_P_1 0.00 0.00 0.00 0.000 0.013 SUMMER 7/22 22:00:00 25.00 24.60 0.01018 29.70 0.01095 0.013 0.00
Z06_ASEO_1 0.0 0.0 0.0 0.0 0.0 N/A N/A 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Z07_ASEO_2 0.0 0.0 0.0 0.0 0.0 N/A N/A 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Z08_ASEO_ACCESIBLE 0.0 0.0 0.0 0.0 0.0 N/A N/A 0.0 0.0 0.0 0.0 0.0 0.0 0.0
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
Z01_RECEPCION_CAFETERIA 0.00 0.00 0.00 0.000 0.024   00:15:00 -50.00 26.23 0.00852 28.02 0.01046 0.024 0.00
Z02_OFICINA 12.60 12.60 2.14 0.000 0.013 WINTER 1/9 09:15:00 20.00 20.15 0.00522 6.35 0.00502 0.013 0.00
Z03_SALAS_DEPORTIVAS 0.00 0.00 0.00 0.000 0.160   00:15:00 -50.00 26.47 0.01127 28.02 0.01046 0.160 0.00
Z04_ZONAS_SECAS_P_1 347.34 347.34 9.85 0.010 0.031 WINTER 1/13 09:00:00 20.00 20.00 0.00775 4.80 0.00441 0.031 0.00
Z05_VESTUARIOS_P_1 638.43 638.43 27.80 0.019 0.019 WINTER 1/13 09:00:00 20.00 20.00 0.00682 4.80 0.00441 0.013 0.00
Z06_ASEO_1 0.0 0.0 0.0 0.0 0.0 N/A N/A 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Z07_ASEO_2 0.0 0.0 0.0 0.0 0.0 N/A N/A 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Z08_ASEO_ACCESIBLE 0.0 0.0 0.0 0.0 0.0 N/A N/A 0.0 0.0 0.0 0.0 0.0 0.0 0.0
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR 0.10 0.02 0.02 0.02 0.0240 0.0240 0.0240 1.0000 1.0000
LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR 0.03 0.01 0.01 0.01 0.0125 0.0125 0.0125 1.0000 1.0000
LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR 0.19 0.16 0.16 0.16 0.1600 0.1600 0.1600 1.0000 1.0000
LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR 0.03 0.03 0.03 0.03 0.0307 0.0307 0.0307 1.0000 1.0000
LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR 0.01 0.01 0.02 0.01 0.0126 0.0126 0.0126 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Coil:Cooling:DX:VariableRefrigerantFlow ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS 1694.234 1356.497 0.102349 -999.0 -999.000 WINTER unknown unknown unknown 1681.20 1658.82 0.102349 25.18 15.63 0.00808461 12.80 10.89 0.00800000 11.40 0.00500494 7.08 0.0000 25.00 0.00808461 37.8826 1415.94 0.00 1926.77 1391.56
UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL Coil:Heating:DX:VariableRefrigerantFlow ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS 1694.234 0.000 0.102349 -999.0 -999.000   unknown   unknown 1694.23 1694.23 0.102349 20.00 13.70 0.00800000 50.00 23.00 0.00800000 23.10 0.01046152 16.88 0.0000 20.00 0.00800000 50.8020 0.00 0.00 1693.25 1693.25
UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Coil:Cooling:DX:VariableRefrigerantFlow ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS 451.243 361.290 0.027260 -999.0 -999.000 SUMMER unknown unknown unknown 449.86 433.41 0.027260 25.18 15.76 0.00823805 12.80 10.89 0.00800000 34.30 0.00978863 19.87 0.0000 25.00 0.00823805 38.5940 377.10 0.00 513.18 370.63
UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL Coil:Heating:DX:VariableRefrigerantFlow ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS 451.243 0.000 0.027260 -999.0 -999.000 WINTER unknown WINTER unknown 451.24 451.24 0.027260 20.15 11.12 0.00521737 50.00 23.00 0.00800000 6.35 0.00502482 4.66 0.0000 20.15 0.00521737 32.9609 12.60 0.00 450.98 450.98
UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Coil:Cooling:DX:VariableRefrigerantFlow ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS 3821.046 2930.349 0.186405 -999.0 -999.000 SUMMER unknown unknown unknown 4102.44 2830.66 0.186405 25.17 17.83 0.01081644 12.80 10.89 0.00800000 31.60 0.01074822 19.75 0.0000 24.99 0.01081644 50.4861 2577.90 0.00 4345.50 3027.30
UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL Coil:Heating:DX:VariableRefrigerantFlow ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS 3821.046 0.000 0.186405 -999.0 -999.000   unknown   unknown 3821.05 3821.05 0.186405 20.00 13.70 0.00800000 50.00 23.00 0.00800000 23.10 0.01046152 16.88 0.0000 20.00 0.00800000 50.8020 0.00 0.00 3818.83 3818.83
UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Coil:Cooling:DX:VariableRefrigerantFlow ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS 603.265 472.136 0.030692 -999.0 -999.000 SUMMER unknown unknown unknown 640.57 462.22 0.030692 25.16 17.52 0.01041772 12.80 10.89 0.00800000 30.90 0.01060551 19.44 0.0000 25.00 0.01041772 48.6343 3.96 0.00 686.07 486.14
UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL Coil:Heating:DX:VariableRefrigerantFlow ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS 603.265 0.000 0.030692 -999.0 -999.000 WINTER unknown WINTER unknown 603.27 603.27 0.030692 20.00 13.48 0.00775025 50.00 23.00 0.00800000 4.80 0.00441475 3.09 0.0000 20.00 0.00775025 49.2361 347.34 0.00 602.92 602.92
UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS COOLING COIL Coil:Cooling:DX:VariableRefrigerantFlow ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS 307.052 245.842 0.018549 -999.0 -999.000 SUMMER unknown unknown unknown 303.90 303.90 0.018549 25.18 15.56 0.00800000 12.80 10.89 0.00800000 23.10 0.01094922 17.27 0.0000 25.00 0.00800000 37.4906 0.00 0.00 349.20 252.20
UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS HEATING COIL Coil:Heating:DX:VariableRefrigerantFlow ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS 307.052 0.000 0.018549 -999.0 -999.000 WINTER unknown WINTER unknown 307.05 307.05 0.018549 20.00 12.62 0.00682165 50.00 23.00 0.00800000 4.80 0.00441475 3.09 0.0000 20.00 0.00682165 43.4068 638.43 0.00 306.87 306.87



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Coil:Cooling:DX:VariableRefrigerantFlow Zone Equipment ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS Z01_RECEPCION_CAFETERIA N/A N/A N/A Yes Yes unknown No 1694.234 1356.497 0.102349 -999.0 -999.000 -999.0000 1.15076 1.00000 1019.8689 1004.8586 1.1121 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WINTER unknown unknown unknown unknown unknown Sensible 1681.20 1658.82 0.9923 0.11381902 0.102349 25.18 15.63 0.00808461 45895.5 12.80 10.89 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 20.470 1660.73 11.40 0.00500494 7.08 0.00000000 0.0000 25.00 0.00808461 25.00 0.00808461 37.8826 1415.94 0.00 1926.77 1391.56 0.10932403 26.67 19.44 0.01118466 55322.4 14.21 13.42 0.00926519 37698.0
UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL Coil:Heating:DX:VariableRefrigerantFlow Zone Equipment ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE1_UNIDAD_INTERIOR_DE_CONDUCTOS Z01_RECEPCION_CAFETERIA N/A N/A N/A Yes Yes unknown No 1694.234 0.000 0.102349 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1121 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0   unknown unknown unknown   unknown Sensible 1694.23 1694.23 1.0000 0.11381902 0.102349 20.00 13.70 0.00800000 40401.8 50.00 23.00 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 1694.23 23.10 0.01046152 16.88 0.00000000 0.0000 20.00 0.00800000 20.00 0.00800000 50.8020 0.00 0.00 1693.25 1693.25 0.11180781 21.11 15.56 0.00875166 43444.1 35.94 20.51 0.00875166 58588.4
UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Coil:Cooling:DX:VariableRefrigerantFlow Zone Equipment ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS Z02_OFICINA N/A N/A N/A Yes Yes unknown No 451.243 361.290 0.027260 -999.0 -999.000 -999.0000 1.12204 1.00000 1020.1541 1004.8586 1.1121 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SUMMER unknown unknown unknown unknown unknown Sensible 449.86 433.41 0.9969 0.03031459 0.027260 25.18 15.76 0.00823805 46285.5 12.80 10.89 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 5.452 444.41 34.30 0.00978863 19.87 0.00000000 0.0000 25.00 0.00823805 25.00 0.00823805 38.5940 377.10 0.00 513.18 370.63 0.02911739 26.67 19.44 0.01118466 55322.4 14.21 13.42 0.00926519 37698.0
UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL Coil:Heating:DX:VariableRefrigerantFlow Zone Equipment ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE2_UNIDAD_INTERIOR_DE_CONDUCTOS Z02_OFICINA N/A N/A N/A Yes Yes unknown No 451.243 0.000 0.027260 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1121 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WINTER unknown unknown unknown WINTER unknown Sensible 451.24 451.24 1.0000 0.03031459 0.027260 20.15 11.12 0.00521737 33496.3 50.00 23.00 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 451.24 6.35 0.00502482 4.66 0.00000000 0.0000 4.74 0.00521737 20.15 0.00521737 32.9609 12.60 0.00 450.98 450.98 0.02977892 21.11 15.56 0.00875166 43444.1 35.94 20.51 0.00875166 58588.4
UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Coil:Cooling:DX:VariableRefrigerantFlow Zone Equipment ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS Z03_SALAS_DEPORTIVAS N/A N/A N/A Yes Yes unknown No 3821.046 2930.349 0.186405 -999.0 -999.000 -999.0000 1.00000 1.00000 1024.9472 1004.8586 1.1121 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SUMMER unknown unknown unknown unknown unknown Sensible 4102.44 2830.66 1.0736 0.20729518 0.186405 25.17 17.83 0.01081644 52850.1 12.80 10.89 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 37.281 4065.15 31.60 0.01074822 19.75 0.00000000 0.0000 24.99 0.01081644 24.99 0.01081644 50.4861 2577.90 0.00 4345.50 3027.30 0.19910859 26.67 19.44 0.01118466 55322.4 11.77 11.76 0.00858892 33497.6
UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL Coil:Heating:DX:VariableRefrigerantFlow Zone Equipment ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE3_UNIDAD_INTERIOR_DE_CONDUCTOS Z03_SALAS_DEPORTIVAS N/A N/A N/A Yes Yes unknown No 3821.046 0.000 0.186405 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1121 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0   unknown unknown unknown   unknown Sensible 3821.05 3821.05 1.0000 0.20729518 0.186405 20.00 13.70 0.00800000 40401.8 50.00 23.00 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 3821.05 23.10 0.01046152 16.88 0.00000000 0.0000 20.00 0.00800000 20.00 0.00800000 50.8020 0.00 0.00 3818.83 3818.83 0.20363221 21.11 15.56 0.00875166 43444.1 39.48 21.57 0.00875166 62197.7
UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS COOLING COIL Coil:Cooling:DX:VariableRefrigerantFlow Zone Equipment ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS Z04_ZONAS_SECAS_P_1 N/A N/A N/A Yes Yes unknown No 603.265 472.136 0.030692 -999.0 -999.000 -999.0000 1.00000 1.00000 1024.2060 1004.8586 1.1121 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SUMMER unknown unknown unknown unknown unknown Sensible 640.57 462.22 1.0618 0.03413170 0.030692 25.16 17.52 0.01041772 51827.4 12.80 10.89 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 6.138 634.43 30.90 0.01060551 19.44 0.00000000 0.0000 25.00 0.01041772 25.00 0.01041772 48.6343 3.96 0.00 686.07 486.14 0.03278376 26.67 19.44 0.01118466 55322.4 12.15 12.12 0.00879361 34395.4
UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS HEATING COIL Coil:Heating:DX:VariableRefrigerantFlow Zone Equipment ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE4_UNIDAD_INTERIOR_DE_CONDUCTOS Z04_ZONAS_SECAS_P_1 N/A N/A N/A Yes Yes unknown No 603.265 0.000 0.030692 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1121 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WINTER unknown unknown unknown WINTER unknown Sensible 603.27 603.27 1.0000 0.03413170 0.030692 20.00 13.48 0.00775025 39767.7 50.00 23.00 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 603.27 4.80 0.00441475 3.09 0.00000000 0.0000 19.92 0.00775025 20.00 0.00775025 49.2361 347.34 0.00 602.92 602.92 0.03352858 21.11 15.56 0.00875166 43444.1 38.72 21.34 0.00875166 61426.3
UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS COOLING COIL Coil:Cooling:DX:VariableRefrigerantFlow Zone Equipment ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS Z05_VESTUARIOS_P_1 N/A N/A N/A Yes Yes unknown No 307.052 245.842 0.018549 -999.0 -999.000 -999.0000 1.16738 1.00000 1019.7116 1004.8586 1.1121 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SUMMER unknown unknown unknown unknown unknown Sensible 303.90 303.90 0.9897 0.02062780 0.018549 25.18 15.56 0.00800000 45680.2 12.80 10.89 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 3.710 300.19 23.10 0.01094922 17.27 0.00000000 0.0000 25.00 0.00800000 25.00 0.00800000 37.4906 0.00 0.00 349.20 252.20 0.01981315 26.67 19.44 0.01118466 55322.4 14.21 13.42 0.00926519 37698.0
UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS HEATING COIL Coil:Heating:DX:VariableRefrigerantFlow Zone Equipment ZONEHVAC:TERMINALUNIT:VARIABLEREFRIGERANTFLOW UT2_ZONE5_UNIDAD_INTERIOR_CON_CONDUCTOS Z05_VESTUARIOS_P_1 N/A N/A N/A Yes Yes unknown No 307.052 0.000 0.018549 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1121 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WINTER unknown unknown unknown WINTER unknown Sensible 307.05 307.05 1.0000 0.02062780 0.018549 20.00 12.62 0.00682165 37408.5 50.00 23.00 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 307.05 4.80 0.00441475 3.09 0.00000000 0.0000 19.87 0.00682165 20.00 0.00682165 43.4068 638.43 0.00 306.87 306.87 0.02026330 21.11 15.56 0.00875166 43444.1 35.94 20.51 0.00875166 58588.4



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR OA CONTROLLER DifferentialDryBulb 0.02 0.02 -      
LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR OA CONTROLLER DifferentialDryBulb 0.01 0.01 -      
LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR OA CONTROLLER DifferentialDryBulb 0.16 0.16 -      
LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR OA CONTROLLER DifferentialDryBulb 0.03 0.03 -      
LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR OA CONTROLLER DifferentialDryBulb 0.01 0.01 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
Z01_RECEPCION_CAFETERIA 2351.75 1006.25 33.00
Z02_OFICINA 1713.00 785.25 98.75
Z03_SALAS_DEPORTIVAS 1707.25 2150.25 296.50
Z04_ZONAS_SECAS_P_1 1766.75 2963.00 1661.25
Z05_VESTUARIOS_P_1 0.00 0.00 0.00
Z06_ASEO_1 0.00 0.00 0.00
Z07_ASEO_2 0.00 0.00 0.00
Z08_ASEO_ACCESIBLE 0.00 0.00 0.00
Z09_ASCENSOR 0.00 0.00 0.00
Facility 3547.50 3277.00 1850.25
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
Z01_RECEPCION_CAFETERIA 0.00 0.50 0.00 0.50
Z02_OFICINA 0.00 8.00 0.00 8.00
Z03_SALAS_DEPORTIVAS 0.00 0.00 0.00 0.00
Z04_ZONAS_SECAS_P_1 4.50 0.00 4.50 0.00
Z05_VESTUARIOS_P_1 1031.50 0.00 0.00 0.00
Z06_ASEO_1 0.00 0.00 0.00 0.00
Z07_ASEO_2 0.00 0.00 0.00 0.00
Z08_ASEO_ACCESIBLE 0.00 0.00 0.00 0.00
Z09_ASCENSOR 0.00 0.00 0.00 0.00
Facility 1031.50 8.50 4.50 8.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
Z01_RECEPCION_CAFETERIA 2.19 3.00 164.65 0.497 0.000 0.000 0.000
Z02_OFICINA 0.85 1.00 20.23 2.106 0.000 0.000 0.000
Z03_SALAS_DEPORTIVAS 12.53 20.00 321.26 1.698 0.000 0.000 0.000
Z04_ZONAS_SECAS_P_1 1.74 2.00 106.77 0.970 0.000 0.000 0.000
Z05_VESTUARIOS_P_1     69.18        
Z06_ASEO_1     10.96        
Z07_ASEO_2     10.71        
Z08_ASEO_ACCESIBLE     33.00        
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
Z01_RECEPCION_CAFETERIA 2.19 3.00 164.65 0.484 0.000 0.000 0.000
Z02_OFICINA 0.85 1.00 20.23 2.044 0.000 0.000 0.000
Z03_SALAS_DEPORTIVAS 12.53 20.00 321.26 1.647 0.000 0.000 0.000
Z04_ZONAS_SECAS_P_1 1.74 2.00 106.77 0.950 0.000 0.000 0.000
Z05_VESTUARIOS_P_1     69.18        
Z06_ASEO_1     10.96        
Z07_ASEO_2     10.71        
Z08_ASEO_ACCESIBLE     33.00        
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
Z01_RECEPCION_CAFETERIA LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR 2.19 3.00 164.65 48.00 0.0000 0.000
Z02_OFICINA LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR 0.85 1.00 20.23 5.90 0.0000 0.000
Z03_SALAS_DEPORTIVAS LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR 12.53 20.00 321.26 93.66 0.0000 0.000
Z04_ZONAS_SECAS_P_1 LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR 1.74 2.00 106.77 35.26 0.0000 0.000
Z05_VESTUARIOS_P_1 LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR   0.00 69.18 22.97 0.0000 0.000
Z06_ASEO_1     0.00 10.96 3.62   0.000
Z07_ASEO_2     0.00 10.71 3.53   0.000
Z08_ASEO_ACCESIBLE     0.00 33.00 9.62   0.000
Total Facility   17.31 26.00 736.75 222.56 0.0000 0.000


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
Z01_RECEPCION_CAFETERIA 324604.80 0.00 324604.80 0.00 324604.80 324604.80 0.00 3757.00 0.00 0.00
Z02_OFICINA 169065.00 0.00 169065.00 0.00 169065.00 169065.00 0.00 3757.00 0.00 1147.00
Z03_SALAS_DEPORTIVAS 2164032.00 0.00 2164032.00 0.00 2164032.00 2164032.00 0.00 3757.00 0.00 0.00
Z04_ZONAS_SECAS_P_1 415115.44 0.00 415115.44 0.00 415115.44 415115.44 0.00 3757.00 0.00 522.00
Z05_VESTUARIOS_P_1 170854.38 0.00 170854.38 0.00 170854.38 170854.38 0.00 3757.00 0.00 3757.00
Z06_ASEO_1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z07_ASEO_2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z08_ASEO_ACCESIBLE 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 3243671.62 0.00 3243671.62 0.00 3243671.62 3243671.62 0.00 3757.00 0.00 3757.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
Z01_RECEPCION_CAFETERIA 0.0240 0.0000 0.0240 0.0000 0.0240 0.0240 0.00 3757.00 0.00
Z02_OFICINA 0.0125 0.0000 0.0125 0.0000 0.0125 0.0125 0.00 2610.00 0.00
Z03_SALAS_DEPORTIVAS 0.1600 0.0000 0.1600 0.0000 0.1600 0.1600 0.00 3757.00 0.00
Z04_ZONAS_SECAS_P_1 0.0307 0.0000 0.0307 0.0000 0.0307 0.0307 0.00 3235.00 0.00
Total Facility 0.2272 0.0000 0.2272 0.0000 0.2272 0.2272 0.00 3757.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR 401439.81 0.00 401439.81 324604.80 0.00 0.00 3757.00 0.00
LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR 209083.23 0.00 209083.23 169065.00 0.00 0.00 3757.00 1147.00
LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR 2676265.39 0.00 2676265.39 2164032.00 0.00 0.00 3757.00 0.00
LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR 513374.61 0.00 513374.61 415115.44 0.00 0.00 3757.00 522.00
LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR 211296.17 0.00 211296.17 170854.38 0.00 0.00 3757.00 3757.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR 0.0297 0.0000 0.0297 0.0240 0.00 0.00 3757.00
LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR 0.0155 0.0000 0.0155 0.0125 0.00 0.00 2610.00
LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR 0.1979 0.0000 0.1979 0.1600 0.00 0.00 3757.00
LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR 0.0380 0.0000 0.0380 0.0307 0.00 0.00 3235.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR 2924.37 832.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR 3162.95 594.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR 3379.48 377.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR 3575.61 181.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR 2738.02 1018.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR 0.0297 0.0297 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR 0.0155 0.0155 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR 0.1979 0.1981 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR 0.0380 0.0380 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Surfaces by Class

Total Outdoors
Wall 82 44
Floor 14 9
Roof 13 3
Internal Mass 7 0
Building Detached Shading 4 4
Fixed Detached Shading 0 0
Window 10 10
Door 0 0
Glass Door 0 0
Shading 10 10
Overhang 5 5
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 5
Conditioned Zones 8
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 898
Defaulted Fields 505
Fields with Defaults 2239
Autosized Fields 131
Autosizable Fields 164
Autocalculated Fields 4
Autocalculatable Fields 223



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 3275.39 0.00 01-JAN-00:15 2050.69 20-AUG-16:15
Electricity:Building 2230.29 0.00 01-JAN-00:15 837.78 02-JAN-18:15
Electricity:Zone:Z01_RECEPCION_CAFETERIA 633.10 0.00 01-JAN-00:15 264.00 02-JAN-19:15
Electricity:SpaceType:GENERAL 2230.29 0.00 01-JAN-00:15 837.78 02-JAN-18:15
InteriorLights:Electricity 1649.44 0.00 01-JAN-00:15 609.88 01-JAN-17:15
InteriorLights:Electricity:Zone:Z01_RECEPCION_CAFETERIA 343.90 0.00 01-JAN-00:15 156.00 01-JAN-19:15
InteriorLights:Electricity:SpaceType:GENERAL 1649.44 0.00 01-JAN-00:15 609.88 01-JAN-17:15
1:InteriorLights:Electricity 1649.44 0.00 01-JAN-00:15 609.88 01-JAN-17:15
1:InteriorLights:Electricity:Zone:Z01_RECEPCION_CAFETERIA 343.90 0.00 01-JAN-00:15 156.00 01-JAN-19:15
1:InteriorLights:Electricity:SpaceType:GENERAL 1649.44 0.00 01-JAN-00:15 609.88 01-JAN-17:15
Electricity:Zone:Z02_OFICINA 109.43 0.00 01-JAN-00:15 43.70 01-JAN-09:15
InteriorLights:Electricity:Zone:Z02_OFICINA 67.86 0.00 01-JAN-00:15 26.00 01-JAN-09:15
1:InteriorLights:Electricity:Zone:Z02_OFICINA 67.86 0.00 01-JAN-00:15 26.00 01-JAN-09:15
Electricity:Zone:Z03_SALAS_DEPORTIVAS 1202.68 0.00 01-JAN-00:15 483.66 01-JAN-18:15
InteriorLights:Electricity:Zone:Z03_SALAS_DEPORTIVAS 976.68 0.00 01-JAN-00:15 390.00 01-JAN-17:15
1:InteriorLights:Electricity:Zone:Z03_SALAS_DEPORTIVAS 976.68 0.00 01-JAN-00:15 390.00 01-JAN-17:15
Electricity:Zone:Z04_ZONAS_SECAS_P_1 191.62 0.00 01-JAN-00:15 60.54 01-JAN-10:15
InteriorLights:Electricity:Zone:Z04_ZONAS_SECAS_P_1 167.54 0.00 01-JAN-00:15 52.00 01-JAN-10:15
1:InteriorLights:Electricity:Zone:Z04_ZONAS_SECAS_P_1 167.54 0.00 01-JAN-00:15 52.00 01-JAN-10:15
Electricity:Zone:Z05_VESTUARIOS_P_1 73.26 0.00 01-JAN-00:15 19.50 01-JAN-09:15
InteriorLights:Electricity:Zone:Z05_VESTUARIOS_P_1 73.26 0.00 01-JAN-00:15 19.50 01-JAN-09:15
1:InteriorLights:Electricity:Zone:Z05_VESTUARIOS_P_1 73.26 0.00 01-JAN-00:15 19.50 01-JAN-09:15
Electricity:Zone:Z06_ASEO_1 4.23 0.00 01-JAN-00:15 1.12 01-JAN-09:15
InteriorLights:Electricity:Zone:Z06_ASEO_1 4.23 0.00 01-JAN-00:15 1.12 01-JAN-09:15
1:InteriorLights:Electricity:Zone:Z06_ASEO_1 4.23 0.00 01-JAN-00:15 1.12 01-JAN-09:15
Electricity:Zone:Z07_ASEO_2 4.23 0.00 01-JAN-00:15 1.13 01-JAN-09:15
InteriorLights:Electricity:Zone:Z07_ASEO_2 4.23 0.00 01-JAN-00:15 1.13 01-JAN-09:15
1:InteriorLights:Electricity:Zone:Z07_ASEO_2 4.23 0.00 01-JAN-00:15 1.13 01-JAN-09:15
Electricity:Zone:Z08_ASEO_ACCESIBLE 11.74 0.00 01-JAN-00:15 3.12 01-JAN-09:15
InteriorLights:Electricity:Zone:Z08_ASEO_ACCESIBLE 11.74 0.00 01-JAN-00:15 3.12 01-JAN-09:15
1:InteriorLights:Electricity:Zone:Z08_ASEO_ACCESIBLE 11.74 0.00 01-JAN-00:15 3.12 01-JAN-09:15
InteriorEquipment:Electricity 580.85 0.00 01-JAN-00:15 246.21 06-JAN-10:15
InteriorEquipment:Electricity:Zone:Z01_RECEPCION_CAFETERIA 289.20 0.00 01-JAN-00:15 144.01 01-JAN-09:15
InteriorEquipment:Electricity:SpaceType:GENERAL 580.85 0.00 01-JAN-00:15 246.21 06-JAN-10:15
General:InteriorEquipment:Electricity 580.85 0.00 01-JAN-00:15 246.21 06-JAN-10:15
General:InteriorEquipment:Electricity:Zone:Z01_RECEPCION_CAFETERIA 289.20 0.00 01-JAN-00:15 144.01 01-JAN-09:15
General:InteriorEquipment:Electricity:SpaceType:GENERAL 580.85 0.00 01-JAN-00:15 246.21 06-JAN-10:15
InteriorEquipment:Electricity:Zone:Z02_OFICINA 41.57 0.00 01-JAN-00:15 17.70 01-JAN-09:15
General:InteriorEquipment:Electricity:Zone:Z02_OFICINA 41.57 0.00 01-JAN-00:15 17.70 01-JAN-09:15
InteriorEquipment:Electricity:Zone:Z03_SALAS_DEPORTIVAS 226.00 0.00 01-JAN-00:15 93.66 01-JAN-18:15
General:InteriorEquipment:Electricity:Zone:Z03_SALAS_DEPORTIVAS 226.00 0.00 01-JAN-00:15 93.66 01-JAN-18:15
InteriorEquipment:Electricity:Zone:Z04_ZONAS_SECAS_P_1 24.08 0.00 01-JAN-00:15 8.54 01-JAN-09:15
General:InteriorEquipment:Electricity:Zone:Z04_ZONAS_SECAS_P_1 24.08 0.00 01-JAN-00:15 8.54 01-JAN-09:15
Fans:Electricity 68.44 0.00 01-JAN-00:15 62.45 23-JUL-08:15
Fans:Electricity:Zone:Z01_RECEPCION_CAFETERIA 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity:Zone:Z01_RECEPCION_CAFETERIA 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:Z02_OFICINA 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity:Zone:Z02_OFICINA 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:Z03_SALAS_DEPORTIVAS 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity:Zone:Z03_SALAS_DEPORTIVAS 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:Z04_ZONAS_SECAS_P_1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity:Zone:Z04_ZONAS_SECAS_P_1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:Z05_VESTUARIOS_P_1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity:Zone:Z05_VESTUARIOS_P_1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:Z08_ASEO_ACCESIBLE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity:Zone:Z08_ASEO_ACCESIBLE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 3275.39 0.00 01-JAN-00:15 2050.69 20-AUG-16:15
ElectricityPurchased:Plant 3275.39 0.00 01-JAN-00:15 2050.69 20-AUG-16:15
Cogeneration:ElectricityPurchased 3275.39 0.00 01-JAN-00:15 2050.69 20-AUG-16:15
General:Cogeneration:ElectricityPurchased 3275.39 0.00 01-JAN-00:15 2050.69 20-AUG-16:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 3275.39 0.00 01-JAN-00:15 2050.69 20-AUG-16:15
ElectricityNet:Plant 3275.39 0.00 01-JAN-00:15 2050.69 20-AUG-16:15
Cogeneration:ElectricityNet 3275.39 0.00 01-JAN-00:15 2050.69 20-AUG-16:15
General:Cogeneration:ElectricityNet 3275.39 0.00 01-JAN-00:15 2050.69 20-AUG-16:15
Electricity:HVAC 1045.10 0.00 01-JAN-00:15 1344.33 20-AUG-16:15
General:Fans:Electricity 68.44 0.00 01-JAN-00:15 62.45 23-JUL-08:15
Cooling:Electricity 803.51 0.00 01-JAN-00:15 1283.39 20-AUG-16:15
General:Cooling:Electricity 803.51 0.00 01-JAN-00:15 1283.39 20-AUG-16:15
Heating:Electricity 173.15 0.00 01-JAN-00:15 1078.64 10-MAR-08:15
General:Heating:Electricity 173.15 0.00 01-JAN-00:15 1078.64 10-MAR-08:15
HeatRecovery:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
General:HeatRecovery:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [kWh] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [kWh] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
DistrictCooling:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
DistrictCooling:HVAC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:DistrictCooling 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
General:Cooling:DistrictCooling 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 505.84 0.00 01-JAN-00:15 0.00 19-FEB-09:15
Water:Plant 505.84 0.00 01-JAN-00:15 0.00 19-FEB-09:15
WaterSystems:Water 505.84 0.00 01-JAN-00:15 0.00 19-FEB-09:15
General:WaterSystems:Water 505.84 0.00 01-JAN-00:15 0.00 19-FEB-09:15
MainsWater:Facility 505.84 0.00 01-JAN-00:15 0.00 19-FEB-09:15
MainsWater:Plant 505.84 0.00 01-JAN-00:15 0.00 19-FEB-09:15
WaterSystems:MainsWater 505.84 0.00 01-JAN-00:15 0.00 19-FEB-09:15
General:WaterSystems:MainsWater 505.84 0.00 01-JAN-00:15 0.00 19-FEB-09:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
CO2:Facility 8371.82 0.000 04-AUG-14:15 0.000 04-SEP-16:15
ElectricityEmissions:CO2 1084.15 0.000 01-JAN-00:15 0.000 20-AUG-16:15
CO:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
ElectricityEmissions:CO 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CH4:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
ElectricityEmissions:CH4 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
NOx:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
ElectricityEmissions:NOx 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
N2O:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
ElectricityEmissions:N2O 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
SO2:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
ElectricityEmissions:SO2 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PM:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
ElectricityEmissions:PM 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PM10:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
ElectricityEmissions:PM10 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PM2.5:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
ElectricityEmissions:PM2.5 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
NH3:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
ElectricityEmissions:NH3 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
NMVOC:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
ElectricityEmissions:NMVOC 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
Hg:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
ElectricityEmissions:Hg 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
Pb:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
ElectricityEmissions:Pb 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
Nuclear High:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
ElectricityEmissions:Nuclear High 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
NaturalGasEmissions:CO2 7287.67 0.000 01-AUG-18:15 0.000 01-JAN-00:15
NaturalGasEmissions:CO 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
NaturalGasEmissions:CH4 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
NaturalGasEmissions:NOx 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
NaturalGasEmissions:N2O 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
NaturalGasEmissions:SO2 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
NaturalGasEmissions:PM 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
NaturalGasEmissions:PM10 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
NaturalGasEmissions:PM2.5 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
NaturalGasEmissions:NH3 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
NaturalGasEmissions:NMVOC 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
NaturalGasEmissions:Hg 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
NaturalGasEmissions:Pb 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
NaturalGasEmissions:Nuclear High 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PropaneEmissions:CO2 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PropaneEmissions:CO 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PropaneEmissions:CH4 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PropaneEmissions:NOx 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PropaneEmissions:N2O 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PropaneEmissions:SO2 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PropaneEmissions:PM 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PropaneEmissions:PM10 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PropaneEmissions:PM2.5 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PropaneEmissions:NH3 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PropaneEmissions:NMVOC 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PropaneEmissions:Hg 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PropaneEmissions:Pb 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PropaneEmissions:Nuclear High 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo1Emissions:CO2 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo1Emissions:CO 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo1Emissions:CH4 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo1Emissions:NOx 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo1Emissions:N2O 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo1Emissions:SO2 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo1Emissions:PM 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo1Emissions:PM10 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo1Emissions:PM2.5 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo1Emissions:NH3 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo1Emissions:NMVOC 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo1Emissions:Hg 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo1Emissions:Pb 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo1Emissions:Nuclear High 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo2Emissions:CO2 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo2Emissions:CO 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo2Emissions:CH4 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo2Emissions:NOx 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo2Emissions:N2O 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo2Emissions:SO2 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo2Emissions:PM 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo2Emissions:PM10 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo2Emissions:PM2.5 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo2Emissions:NH3 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo2Emissions:NMVOC 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo2Emissions:Hg 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo2Emissions:Pb 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo2Emissions:Nuclear High 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CoalEmissions:CO2 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CoalEmissions:CO 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CoalEmissions:CH4 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CoalEmissions:NOx 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CoalEmissions:N2O 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CoalEmissions:SO2 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CoalEmissions:PM 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CoalEmissions:PM10 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CoalEmissions:PM2.5 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CoalEmissions:NH3 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CoalEmissions:NMVOC 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CoalEmissions:Hg 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CoalEmissions:Pb 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CoalEmissions:Nuclear High 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
DieselEmissions:CO2 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
DieselEmissions:CO 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
DieselEmissions:CH4 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
DieselEmissions:NOx 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
DieselEmissions:N2O 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
DieselEmissions:SO2 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
DieselEmissions:PM 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
DieselEmissions:PM10 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
DieselEmissions:PM2.5 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
DieselEmissions:NH3 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
DieselEmissions:NMVOC 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
DieselEmissions:Hg 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
DieselEmissions:Pb 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
DieselEmissions:Nuclear High 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
GasolineEmissions:CO2 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
GasolineEmissions:CO 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
GasolineEmissions:CH4 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
GasolineEmissions:NOx 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
GasolineEmissions:N2O 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
GasolineEmissions:SO2 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
GasolineEmissions:PM 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
GasolineEmissions:PM10 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
GasolineEmissions:PM2.5 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
GasolineEmissions:NH3 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
GasolineEmissions:NMVOC 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
GasolineEmissions:Hg 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
GasolineEmissions:Pb 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
GasolineEmissions:Nuclear High 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel1Emissions:CO2 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel1Emissions:CO 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel1Emissions:CH4 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel1Emissions:NOx 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel1Emissions:N2O 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel1Emissions:SO2 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel1Emissions:PM 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel1Emissions:PM10 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel1Emissions:PM2.5 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel1Emissions:NH3 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel1Emissions:NMVOC 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel1Emissions:Hg 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel1Emissions:Pb 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel1Emissions:Nuclear High 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel2Emissions:CO2 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel2Emissions:CO 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel2Emissions:CH4 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel2Emissions:NOx 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel2Emissions:N2O 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel2Emissions:SO2 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel2Emissions:PM 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel2Emissions:PM10 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel2Emissions:PM2.5 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel2Emissions:NH3 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel2Emissions:NMVOC 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel2Emissions:Hg 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel2Emissions:Pb 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel2Emissions:Nuclear High 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
Carbon Equivalent:Facility 2282.99 0.000 04-AUG-14:15 0.000 04-SEP-16:15
CarbonEquivalentEmissions:Carbon Equivalent 2282.99 0.000 04-AUG-14:15 0.000 04-SEP-16:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Nuclear Low:Facility 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
ElectricityEmissions:Nuclear Low 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
NaturalGasEmissions:Nuclear Low 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PropaneEmissions:Nuclear Low 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo1Emissions:Nuclear Low 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo2Emissions:Nuclear Low 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CoalEmissions:Nuclear Low 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
DieselEmissions:Nuclear Low 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
GasolineEmissions:Nuclear Low 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel1Emissions:Nuclear Low 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel2Emissions:Nuclear Low 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
WaterEnvironmentalFactors:Facility 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
ElectricityEmissions:WaterEnvironmentalFactors 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
NaturalGasEmissions:WaterEnvironmentalFactors 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
PropaneEmissions:WaterEnvironmentalFactors 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo1Emissions:WaterEnvironmentalFactors 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
FuelOilNo2Emissions:WaterEnvironmentalFactors 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CoalEmissions:WaterEnvironmentalFactors 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
DieselEmissions:WaterEnvironmentalFactors 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
GasolineEmissions:WaterEnvironmentalFactors 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel1Emissions:WaterEnvironmentalFactors 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15
OtherFuel2Emissions:WaterEnvironmentalFactors 0.000 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other

Annual Value [kWh] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 14609.92 0.00 01-JAN-00:15 12493.26 20-AUG-16:15
EnergyTransfer:Building 6905.43 0.00 01-JAN-00:15 5097.65 20-AUG-08:15
EnergyTransfer:Zone:Z01_RECEPCION_CAFETERIA 1850.03 0.00 01-JAN-00:15 1925.24 24-DEC-14:15
Heating:EnergyTransfer 534.94 0.00 01-JAN-00:15 3849.15 19-FEB-09:15
Heating:EnergyTransfer:Zone:Z01_RECEPCION_CAFETERIA 1.05 0.00 01-JAN-00:15 598.21 19-FEB-09:15
General:Heating:EnergyTransfer 534.94 0.00 01-JAN-00:15 3849.15 19-FEB-09:15
General:Heating:EnergyTransfer:Zone:Z01_RECEPCION_CAFETERIA 1.05 0.00 01-JAN-00:15 598.21 19-FEB-09:15
Cooling:EnergyTransfer 6370.48 0.00 01-JAN-00:15 5097.65 20-AUG-08:15
Cooling:EnergyTransfer:Zone:Z01_RECEPCION_CAFETERIA 1848.98 0.00 01-JAN-00:15 1925.24 24-DEC-14:15
General:Cooling:EnergyTransfer 6370.48 0.00 01-JAN-00:15 5097.65 20-AUG-08:15
General:Cooling:EnergyTransfer:Zone:Z01_RECEPCION_CAFETERIA 1848.98 0.00 01-JAN-00:15 1925.24 24-DEC-14:15
EnergyTransfer:Zone:Z02_OFICINA 529.00 0.00 01-JAN-00:15 485.87 20-NOV-12:30
Heating:EnergyTransfer:Zone:Z02_OFICINA 2.18 0.00 01-JAN-00:15 249.78 19-FEB-09:15
General:Heating:EnergyTransfer:Zone:Z02_OFICINA 2.18 0.00 01-JAN-00:15 249.78 19-FEB-09:15
Cooling:EnergyTransfer:Zone:Z02_OFICINA 526.83 0.00 01-JAN-00:15 485.87 20-NOV-12:30
General:Cooling:EnergyTransfer:Zone:Z02_OFICINA 526.83 0.00 01-JAN-00:15 485.87 20-NOV-12:30
EnergyTransfer:Zone:Z03_SALAS_DEPORTIVAS 3954.52 0.00 01-JAN-00:15 3134.36 20-AUG-08:15
Heating:EnergyTransfer:Zone:Z03_SALAS_DEPORTIVAS 15.63 0.00 01-JAN-00:15 2091.44 19-FEB-09:15
General:Heating:EnergyTransfer:Zone:Z03_SALAS_DEPORTIVAS 15.63 0.00 01-JAN-00:15 2091.44 19-FEB-09:15
Cooling:EnergyTransfer:Zone:Z03_SALAS_DEPORTIVAS 3938.89 0.00 01-JAN-00:15 3134.36 20-AUG-08:15
General:Cooling:EnergyTransfer:Zone:Z03_SALAS_DEPORTIVAS 3938.89 0.00 01-JAN-00:15 3134.36 20-AUG-08:15
EnergyTransfer:Zone:Z04_ZONAS_SECAS_P_1 220.79 0.00 01-JAN-00:15 580.91 19-FEB-09:15
Heating:EnergyTransfer:Zone:Z04_ZONAS_SECAS_P_1 173.61 0.00 01-JAN-00:15 580.91 19-FEB-09:15
General:Heating:EnergyTransfer:Zone:Z04_ZONAS_SECAS_P_1 173.61 0.00 01-JAN-00:15 580.91 19-FEB-09:15
Cooling:EnergyTransfer:Zone:Z04_ZONAS_SECAS_P_1 47.17 0.00 01-JAN-00:15 340.56 04-AUG-07:15
General:Cooling:EnergyTransfer:Zone:Z04_ZONAS_SECAS_P_1 47.17 0.00 01-JAN-00:15 340.56 04-AUG-07:15
EnergyTransfer:Zone:Z05_VESTUARIOS_P_1 351.09 0.00 01-JAN-00:15 342.22 19-FEB-18:00
Heating:EnergyTransfer:Zone:Z05_VESTUARIOS_P_1 342.48 0.00 01-JAN-00:15 342.22 19-FEB-18:00
General:Heating:EnergyTransfer:Zone:Z05_VESTUARIOS_P_1 342.48 0.00 01-JAN-00:15 342.22 19-FEB-18:00
Cooling:EnergyTransfer:Zone:Z05_VESTUARIOS_P_1 8.62 0.00 01-JAN-00:15 103.74 03-AUG-08:15
General:Cooling:EnergyTransfer:Zone:Z05_VESTUARIOS_P_1 8.62 0.00 01-JAN-00:15 103.74 03-AUG-08:15
EnergyTransfer:Zone:Z06_ASEO_1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:Z06_ASEO_1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
General:Heating:EnergyTransfer:Zone:Z06_ASEO_1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:Z06_ASEO_1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
General:Cooling:EnergyTransfer:Zone:Z06_ASEO_1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:Z07_ASEO_2 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:Z07_ASEO_2 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
General:Heating:EnergyTransfer:Zone:Z07_ASEO_2 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:Z07_ASEO_2 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
General:Cooling:EnergyTransfer:Zone:Z07_ASEO_2 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:Z08_ASEO_ACCESIBLE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:Z08_ASEO_ACCESIBLE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
General:Heating:EnergyTransfer:Zone:Z08_ASEO_ACCESIBLE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:Z08_ASEO_ACCESIBLE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
General:Cooling:EnergyTransfer:Zone:Z08_ASEO_ACCESIBLE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:Z09_ASCENSOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:Z09_ASCENSOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
General:Heating:EnergyTransfer:Zone:Z09_ASCENSOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:Z09_ASCENSOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
General:Cooling:EnergyTransfer:Zone:Z09_ASCENSOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
DistrictHeating:Facility 26605.79 2681.45 31-JUL-23:15 3284.43 01-JAN-00:15
DistrictHeating:Plant 26605.79 2681.45 31-JUL-23:15 3284.43 01-JAN-00:15
WaterSystems:DistrictHeating 26605.79 2681.45 31-JUL-23:15 3284.43 01-JAN-00:15
General:WaterSystems:DistrictHeating 26605.79 2681.45 31-JUL-23:15 3284.43 01-JAN-00:15
EnergyTransfer:HVAC 7704.49 0.00 01-JAN-00:15 7966.73 20-AUG-16:15
CoolingCoils:EnergyTransfer 4290.43 0.00 01-JAN-00:15 6504.95 23-JUL-08:15
HeatingCoils:EnergyTransfer 580.00 0.00 01-JAN-00:15 4633.84 19-FEB-09:15
DistrictHeating:HVAC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:DistrictHeating 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
General:Heating:DistrictHeating 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
HeatRecoveryForHeating:EnergyTransfer 2097.90 0.00 01-JAN-00:15 3703.67 12-JAN-22:00
HeatRecoveryForCooling:EnergyTransfer 736.16 0.00 01-JAN-00:15 2165.89 21-JUL-14:00
Source:Facility 15512.22 0.00 01-JAN-00:15 9712.06 20-AUG-16:15
ElectricityEmissions:Source 7756.11 0.00 01-JAN-00:15 4856.03 20-AUG-16:15
PurchasedElectricityEmissions:Source 7756.11 0.00 01-JAN-00:15 4856.03 20-AUG-16:15
SoldElectricityEmissions:Source 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
NaturalGasEmissions:Source 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PropaneEmissions:Source 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
FuelOilNo1Emissions:Source 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
FuelOilNo2Emissions:Source 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
CoalEmissions:Source 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
DieselEmissions:Source 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
GasolineEmissions:Source 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
OtherFuel1Emissions:Source 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
OtherFuel2Emissions:Source 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kWh] HVAC Zone Eq & Other Sensible Air Cooling [kWh] HVAC Terminal Unit Sensible Air Heating [kWh] HVAC Terminal Unit Sensible Air Cooling [kWh] HVAC Input Heated Surface Heating [kWh] HVAC Input Cooled Surface Cooling [kWh] People Sensible Heat Addition [kWh] Lights Sensible Heat Addition [kWh] Equipment Sensible Heat Addition [kWh] Window Heat Addition [kWh] Interzone Air Transfer Heat Addition [kWh] Infiltration Heat Addition [kWh] Opaque Surface Conduction and Other Heat Addition [kWh] Equipment Sensible Heat Removal [kWh] Window Heat Removal [kWh] Interzone Air Transfer Heat Removal [kWh] Infiltration Heat Removal [kWh] Opaque Surface Conduction and Other Heat Removal [kWh]
Z01_RECEPCION_CAFETERIA 1.600 -1387.56 21.521 -483.49 0.000 0.000 520.978 343.901 289.200 3540.340 0.000 1.816 0.154 0.000 -869.72 0.000 -215.88 -1762.71
Z02_OFICINA 2.256 -324.70 9.292 -211.50 0.000 0.000 143.371 67.863 41.570 1219.733 0.000 0.298 0.029 0.000 -305.52 0.000 -87.79 -554.88
Z03_SALAS_DEPORTIVAS 36.914 -2053.60 143.610 -2050.44 0.000 0.000 3550.101 976.678 225.999 3887.252 0.000 6.198 0.035 0.000 -1072.92 0.000 -418.38 -3231.42
Z04_ZONAS_SECAS_P_1 197.209 -0.38 45.129 -115.52 0.000 0.000 309.925 167.544 24.075 0.000 0.000 0.256 0.007 0.000 0.000 0.000 -4.02 -624.22
Z05_VESTUARIOS_P_1 345.747 0.000 25.445 -37.33 0.000 0.000 0.000 73.262 0.000 0.000 0.000 6.651 0.005 0.000 0.000 0.000 -26.94 -386.83
Z06_ASEO_1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 4.226 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -4.23
Z07_ASEO_2 0.000 0.000 0.000 0.000 0.000 0.000 0.000 4.227 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -4.23
Z08_ASEO_ACCESIBLE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 11.740 0.000 77.634 0.000 5.437 0.006 0.000 -18.99 0.000 -42.18 -33.64
Z09_ASCENSOR 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Total Facility 583.726 -3766.23 244.996 -2898.28 0.000 0.000 4524.375 1649.442 580.845 8724.959 0.000 20.656 0.235 0.000 -2267.15 0.000 -795.19 -6602.14


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
Z01_RECEPCION_CAFETERIA 24-DEC-14:15 0.00 -1586.28 0.00 -387.71 0.00 0.00 170.76 39.00 144.01 3197.39 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -1577.17
Z02_OFICINA 10-DEC-13:24 0.00 -373.66 0.00 -141.06 0.00 0.00 61.10 26.00 17.70 855.15 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -445.23
Z03_SALAS_DEPORTIVAS 13-AUG-08:15 0.00 -3441.58 0.00 -1067.46 0.00 0.00 310.97 117.00 23.41 339.35 0.00 0.00 3718.32 0.00 -0.00 0.00 0.00 0.00
Z04_ZONAS_SECAS_P_1 04-AUG-07:15 0.00 0.00 0.00 -348.22 0.00 0.00 55.00 39.00 4.27 0.00 0.00 0.00 249.94 0.00 -0.00 0.00 0.00 0.00
Z05_VESTUARIOS_P_1 03-AUG-08:15 0.00 0.00 0.00 -105.32 0.00 0.00 0.00 19.50 0.00 0.00 0.00 0.00 91.44 0.00 -0.00 0.00 -5.62 0.00
Z06_ASEO_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z07_ASEO_2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z08_ASEO_ACCESIBLE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z09_ASCENSOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 22-AUG-08:15 0.00 -5306.68 0.00 -1741.98 0.00 0.00 498.74 245.88 85.66 516.27 0.00 0.00 5712.25 0.00 0.00 0.00 -10.13 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
Z01_RECEPCION_CAFETERIA 19-FEB-09:15 1747.50 79.35 0.00 -79.35 0.00 0.00 52.50 39.00 144.01 446.73 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2429.74
Z02_OFICINA 19-FEB-09:15 451.69 43.49 0.00 -43.49 0.00 0.00 60.00 26.00 17.70 307.21 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -862.60
Z03_SALAS_DEPORTIVAS 19-FEB-09:16 3591.43 559.65 0.00 -559.65 0.00 0.00 518.89 117.00 23.41 694.03 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -4944.76
Z04_ZONAS_SECAS_P_1 19-FEB-17:00 610.48 42.17 0.00 -42.17 0.00 0.00 110.00 52.00 8.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -781.03
Z05_VESTUARIOS_P_1 19-FEB-17:00 345.61 8.84 0.00 -8.84 0.00 0.00 0.00 19.50 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -0.20 -364.91
Z06_ASEO_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z07_ASEO_2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z08_ASEO_ACCESIBLE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z09_ASCENSOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 19-FEB-09:15 6517.42 719.31 0.00 -719.31 0.00 0.00 741.39 245.88 193.66 1455.23 0.00 0.00 0.00 0.00 0.00 0.00 -11.79 -9141.80



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR 0.0240 0.0000 3.0000 1.0000 Calculated from schedules 0.0000 0.0240 0.0000 1.0000 Not calculated 0.0240 1.0000    
LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR 0.0125 0.0000 1.0000 1.0000 Calculated from schedules 0.0000 0.0125 0.0000 1.0000 Not calculated 0.0125 1.0000    
LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR 0.1600 0.0000 20.0000 1.0000 Calculated from schedules 0.0000 0.1600 0.0000 1.0000 Not calculated 0.1600 1.0000    
LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR 0.0307 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 0.0307 0.0000 1.0000 Not calculated 0.0307 1.0000    
LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR 0.0126 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 0.0126 0.0000 1.0000 Not calculated 0.0126 1.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR 0.0240 0.0000 3.0000 1.0000 Calculated from schedules 0.0000 0.0240 0.0000 1.0000 Not calculated 0.0240 1.0000    
LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR 0.0125 0.0000 1.0000 1.0000 Calculated from schedules 0.0000 0.0125 0.0000 1.0000 Not calculated 0.0125 1.0000    
LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR 0.1600 0.0000 20.0000 1.0000 Calculated from schedules 0.0000 0.1600 0.0000 1.0000 Not calculated 0.1600 1.0000    
LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR 0.0307 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 0.0307 0.0000 1.0000 Not calculated 0.0307 1.0000    
LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR 0.0126 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 0.0126 0.0000 1.0000 Not calculated 0.0126 1.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
Z01_RECEPCION_CAFETERIA LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR 0.000000 3.0000 0.000000 48.00 0.0000 1.0000 0.0000 1.000 0.0000
Z02_OFICINA LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR 0.000000 1.0000 0.000000 5.90 0.0000 1.0000 0.0000 1.000 0.0000
Z03_SALAS_DEPORTIVAS LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR 0.000000 20.0000 0.000000 93.66 0.0000 1.0000 0.0000 1.000 0.0000
Z04_ZONAS_SECAS_P_1 LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR 0.000000 2.0000 0.000000 35.26 0.0000 1.0000 0.0000 1.000 0.0000
Z05_VESTUARIOS_P_1 LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR 0.000000 0.0000 0.000000 22.97 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR 0.000000 3.00 0.000000 48.0020 0.0000 0.0000 0.0000
LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR 0.000000 1.00 0.000000 5.8990 0.0000 0.0000 0.0000
LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR 0.000000 20.00 0.000000 93.6590 0.0000 0.0000 0.0000
LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR 0.000000 2.00 0.000000 35.2580 0.0000 0.0000 0.0000
LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR   0.00 0.000000 22.9680 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
Z01_RECEPCION_CAFETERIA LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0240 0.0240 0.0240 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
Z02_OFICINA LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0125 0.0125 0.0125 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
Z03_SALAS_DEPORTIVAS LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.1600 0.1600 0.1600 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
Z04_ZONAS_SECAS_P_1 LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0307 0.0307 0.0307 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
Z05_VESTUARIOS_P_1 LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0126 0.0126 0.0126 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR 0.0240 0.0240 0.0240 0.0240 0.0000 1.0000
LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR 0.0125 0.0125 0.0125 0.0125 0.0000 1.0000
LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR 0.1600 0.1600 0.1600 0.1600 0.0000 1.0000
LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR 0.0307 0.0307 0.0307 0.0307 0.0000 1.0000
LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR 0.0126 0.0126 0.0126 0.0126 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
Z01_RECEPCION_CAFETERIA LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0240 0.0240 0.0240 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
Z02_OFICINA LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0125 0.0125 0.0125 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
Z03_SALAS_DEPORTIVAS LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.1600 0.1600 0.1600 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
Z04_ZONAS_SECAS_P_1 LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0307 0.0307 0.0307 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
Z05_VESTUARIOS_P_1 LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0126 0.0126 0.0126 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
LOOP_VENT1_UT1_ZONE1_Z01_RECEPCION_CAFETERIA_RECUPERACION_DE_CALOR 0.0240 0.0240 0.0240 0.0240 0.0000 1.0000
LOOP_VENT2_UT1_ZONE2_Z02_OFICINA_RECUPERACION_DE_CALOR 0.0125 0.0125 0.0125 0.0125 0.0000 1.0000
LOOP_VENT3_UT1_ZONE3_Z03_SALAS_DEPORTIVAS_RECUPERACION_DE_CALOR 0.1600 0.1600 0.1600 0.1600 0.0000 1.0000
LOOP_VENT4_UT1_ZONE4_Z04_ZONAS_SECAS_P_1_RECUPERACION_DE_CALOR 0.0307 0.0307 0.0307 0.0307 0.0000 1.0000
LOOP_VENT5_UT1_ZONE5_Z05_VESTUARIOS_P_1_RECUPERACION_DE_CALOR 0.0126 0.0126 0.0126 0.0126 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** B3_peninsula - ESP CTE_DB_HE WMO#=
Total gross floor area [m2] 226.15
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
Z01_RECEPCION_CAFETERIA 48.00 48.00 0.00 72.05
Z02_OFICINA 5.90 5.90 0.00 50.05
Z03_SALAS_DEPORTIVAS 93.66 93.66 0.00 72.05
Z04_ZONAS_SECAS_P_1 35.26 35.26 0.00 62.04
Z05_VESTUARIOS_P_1 22.97 22.97 0.00 0.00
Z06_ASEO_1 3.62 3.62 0.00 0.00
Z07_ASEO_2 3.53 3.53 0.00 0.00
Z08_ASEO_ACCESIBLE 9.62 9.62 0.00 0.00
Z09_ASCENSOR 3.59 0.00 3.59 0.00
Totals 226.15 222.56 3.59  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 4.50
Number of hours cooling loads not met 8.50
Number of hours not met 13.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [kWh] Electricity Demand [W] Natural Gas Energy Use [kWh] Natural Gas Demand [W] Gasoline Use [kWh] Gasoline Demand [W] Diesel Use [kWh] Diesel Demand [W] Coal Use [kWh] Coal Demand [W] Fuel Oil No 1 Use [kWh] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [kWh] Fuel Oil No 2 Demand [W] Propane Use [kWh] Propane Demand [W] Other Fuel 1 Use [kWh] Other Fuel 1 Demand [W] Other Fuel 2 Use [kWh] Other Fuel 2 Demand [W] District Cooling Use [kWh] District Cooling Demand [W] District Heating Use [kWh] District Heating Demand [W]
Heating -- General 173.15 1078.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 803.51 1283.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- 1 1649.44 609.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- General 580.85 246.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 68.44 62.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26605.79 3284.43
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [kWh] Total Energy Use [kWh]
Electricity 580.85 3275.39
Natural Gas 0.00 0.00
Additional 0.00 26605.79
Total 580.85 29881.17


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kWh]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/m2]
Interior Lighting (All) 7.29
Space Heating 0.77
Space Cooling 3.55
Fans (All) 0.30
Service Water Heating 0.00
Receptacle Equipment 2.57
Miscellaneous (All) 14.48
Subtotal 14.48


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/m2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [kWh/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 5.52
Space Heating 0.58
Space Cooling 2.69
Fans (All) 0.23
Service Water Heating 89.04
Receptacle Equipment 1.94
Miscellaneous 0.00


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
SCHED2_FLOW_RATE_FRACTION 8760. 8760.
SCHED4 2752. 3757.
SCHED5 2204. 4642.
SCHED6 2008. 3439.
SCHED7 3757. 3757.
SCHED8 5003. 5003.
SCHED11 2218. 2610.
SCHED12 2610. 2610.
SCHED13 2349. 2610.
SCHED14 2361. 3757.
SCHED15 2504. 4642.
SCHED16 2413. 3757.
SCHED19 2818. 3235.
SCHED20 1813. 3757.
SCHED21 939. 3757.
WORK EFF SCH 0. 0.
CLOTHING SCH 8760. 8760.
AIR VELO SCH 1200. 8760.
SUMMERNIGHTVENTILATION SCH 976. 976.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
SCHED0_CTE THERMOSTAT_Z01_RECEPCION_CAFETERIA SETPOINT January 20.00 365 -50.00 365
SCHED1_CTE THERMOSTAT_Z01_RECEPCION_CAFETERIA SETPOINT July 25.00 365 100.00 365
SCHED9_CTE THERMOSTAT_Z02_OFICINA SETPOINT January 20.00 365 -50.00 365
SCHED10_CTE THERMOSTAT_Z02_OFICINA SETPOINT July 25.00 365 100.00 365
SCHED17_CTE THERMOSTAT_Z04_ZONAS_SECAS_P_1 SETPOINT January 20.00 365 -50.00 365
SCHED18_CTE THERMOSTAT_Z04_ZONAS_SECAS_P_1 SETPOINT July 25.00 365 100.00 365
THERMOSTAT_Z06_ASEO_1 HEATING SETPOINT TEMPERATURE THERMOSTAT_Z06_ASEO_1 SETPOINT January -50.00 365 -50.00 365
THERMOSTAT_Z06_ASEO_1 COOLING SETPOINT TEMPERATURE THERMOSTAT_Z06_ASEO_1 SETPOINT July 100.00 365 100.00 365
THERMOSTAT_Z07_ASEO_2 HEATING SETPOINT TEMPERATURE THERMOSTAT_Z07_ASEO_2 SETPOINT January -50.00 365 -50.00 365
THERMOSTAT_Z07_ASEO_2 COOLING SETPOINT TEMPERATURE THERMOSTAT_Z07_ASEO_2 SETPOINT July 100.00 365 100.00 365
THERMOSTAT_Z08_ASEO_ACCESIBLE HEATING SETPOINT TEMPERATURE THERMOSTAT_Z08_ASEO_ACCESIBLE SETPOINT January -50.00 365 -50.00 365
THERMOSTAT_Z08_ASEO_ACCESIBLE COOLING SETPOINT TEMPERATURE THERMOSTAT_Z08_ASEO_ACCESIBLE SETPOINT July 100.00 365 100.00 365



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupiedHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2026-07-17 10:27:17

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupiedHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None